Plan Review Notes For Permit 07020045 |
Permit Number |
07020045 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-02-12 16:00:36 | *** DENIED *** | | 1) PLEASE SHOW ON ENERGY CALCULATIONS CORRECT ADDRESS | | (WEST PALM BEACH) AND ALSO SHOW JURISDICTION NUMBER. | | | | 2) SEE FIRST FLOOR MECH. PAGE 8.1, 8" RETURN AIR | | TRANSFER DUCT TO BEDROOM #1 NEEDS TO BE 10", SEE 2004 | | FBC/R M1602.4. | | | | 3) SEE SECOND FLOOR MECH. PAGE 8.1, 14" RETURN AIR DUCT | | (FLEX) OVER ACCESS PANEL (TO AIR HANDLER). PLEASE | | REMOVE FROM PLANS OR SHOW HOW THE DUCT IS GOING TO GET | | TO THE AIR HANDLER. | | | | 4) 9" RETURN AIR TRANSFER DUCT TO MASTER SUITE NEEDS TO | | BE 16", SEE 2004 FBC/R M1602.4. | | | | *** 2004 FBC/R M1602.4. BALANCED RETURN AIR MAY BE | | ACHIEVED BY. | | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE | | RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS | | SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT | | ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR | | HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO | | ACHIEVE PROPER RETURN AIR BALANCE. | | (C)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET | | THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR | | EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY | | ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE | | SHALL BE INCLUDED. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|