2007-02-12 16:00:36*** DENIED ***
 1) PLEASE SHOW ON ENERGY CALCULATIONS CORRECT ADDRESS
 (WEST PALM BEACH) AND ALSO SHOW JURISDICTION NUMBER.
  
 2) SEE FIRST FLOOR MECH. PAGE 8.1, 8" RETURN AIR
 TRANSFER DUCT TO BEDROOM #1 NEEDS TO BE 10", SEE 2004
 FBC/R M1602.4.
  
 3) SEE SECOND FLOOR MECH. PAGE 8.1, 14" RETURN AIR DUCT
 (FLEX) OVER ACCESS PANEL (TO AIR HANDLER). PLEASE
 REMOVE FROM PLANS OR SHOW HOW THE DUCT IS GOING TO GET
 TO THE AIR HANDLER.
  
 4) 9" RETURN AIR TRANSFER DUCT TO MASTER SUITE NEEDS TO
 BE 16", SEE 2004 FBC/R M1602.4.
  
 *** 2004 FBC/R M1602.4. BALANCED RETURN AIR MAY BE
 ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS
 SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR
 HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO
 ACHIEVE PROPER RETURN AIR BALANCE.
 (C)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET
 THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR
 EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY
 ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.