Plan Review Notes
Plan Review Notes For Permit 07020045
Permit Number 07020045
Review Stop E
Sequence Number 1
Notes
Date Text
2007-02-08 12:16:22 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT. ELECTRICAL NOTE #15 DOES NOT
 SATISFY THIS REQUIREMENT.
  
 2} THE REFERENCE TO THE 2002NEC IS ALSO INCORRECT IN
 THAT NOTE. THE 2005 NEC WAS ADOPTED BY THE FLORIDA
 LEGISLATURE EFFECTIVE 8 DECEMBER 2006. THE APPLICATION
 FOR THIS PROJECT WAS AFTER THAT DATE AND THE PLANS ARE
 SUBJECT TO THAT CODE. PLEASE CHANGE ALL NOTES TO
 REFLECT THIS CHANGE.
  
 3} THE RISER DIAGRAM IS UNCLEAR ON HOW THE SERVICE
 ENTRANCE CONDUCTORS ROUTE TO THE MAIN BREAKER. IF THEY
 ROUTE OVERHEAD THROUGH THE RESIDENCE, THEN A MAIN
 DISCONNECT IS REQUIRED AT THE METER. SEE 230.70(A)(1).
 IF THEY ARE UNDER THE BUILDING THE MAIN IN THE PANEL
 WOULD BE ACCEPTABLE. PLEASE CLARIFY AND ADD THE
 DISCONNECT IF NECESSARY.
  
 4} THE NOTE AT THE RISER INDICATING A DETACHED GARAGE
 WOULD MAKE IT NECESSARY TO SHOW THAT FEED ON THE RISER
 AND INDICATE WHERE THE OCP IS LOCATED. IF FED FROM THE
 PANEL ADD TO THE SCHEDULWE.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 CONSTRUCTION SERVICES DEPARTMENT
 561) 805-6718