2007-02-08 12:16:22 | |
| |
| NONCOMPLIANT |
| |
| PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| COMPLIANCE AND RESUBMIT FOR REVIEW. |
| |
| 1} PER 110.9 AND 110.10: OBTAIN THE |
| AVAILABLE FAULT CURRENT AT THE UTILITY |
| AND CALCULATE THE SAME AT THE EQUIPMENT. |
| INDICATE THE AIC RATING FOR THE |
| EQUIPMENT IS EQUAL TO OR GREATER THAN |
| THE AVAILABLE FAULT. ELECTRICAL NOTE #15 DOES NOT |
| SATISFY THIS REQUIREMENT. |
| |
| 2} THE REFERENCE TO THE 2002NEC IS ALSO INCORRECT IN |
| THAT NOTE. THE 2005 NEC WAS ADOPTED BY THE FLORIDA |
| LEGISLATURE EFFECTIVE 8 DECEMBER 2006. THE APPLICATION |
| FOR THIS PROJECT WAS AFTER THAT DATE AND THE PLANS ARE |
| SUBJECT TO THAT CODE. PLEASE CHANGE ALL NOTES TO |
| REFLECT THIS CHANGE. |
| |
| 3} THE RISER DIAGRAM IS UNCLEAR ON HOW THE SERVICE |
| ENTRANCE CONDUCTORS ROUTE TO THE MAIN BREAKER. IF THEY |
| ROUTE OVERHEAD THROUGH THE RESIDENCE, THEN A MAIN |
| DISCONNECT IS REQUIRED AT THE METER. SEE 230.70(A)(1). |
| IF THEY ARE UNDER THE BUILDING THE MAIN IN THE PANEL |
| WOULD BE ACCEPTABLE. PLEASE CLARIFY AND ADD THE |
| DISCONNECT IF NECESSARY. |
| |
| 4} THE NOTE AT THE RISER INDICATING A DETACHED GARAGE |
| WOULD MAKE IT NECESSARY TO SHOW THAT FEED ON THE RISER |
| AND INDICATE WHERE THE OCP IS LOCATED. IF FED FROM THE |
| PANEL ADD TO THE SCHEDULWE. |
| |
| WILLIAM R. TROBAUGH |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| CONSTRUCTION SERVICES DEPARTMENT |
| 561) 805-6718 |