Plan Review Notes
Plan Review Notes For Permit 07020045
Permit Number 07020045
Review Stop B
Sequence Number 1
Notes
Date Text
2007-03-21 18:54:48BUILDING REVIEWCHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC 713.13
 FLORIDA STATUTE.
  
 2- BRING PLANS TO PALM BEACH COUNTY FOR IMPACT FEES.
 BRING BACK STAMPED PLANS AND COPY OF PAID RECEIPT.
 ***NOTE: MAKE SURE CORRECT BUILDING AREA IS SHOWN ON
 PLANS.
  
 3- SHEET A-1.0: DRIVEWAY APPROACH IS NOT SHOWN
 CORRECTLY. ALSO, CONTACT ENGINEERING DEPARTMENT AT
 (561) 494-1040 FOR DRIVEWAY AND APPROACH STANDARDS.
  
 4- ENERGY CALCULATIONS:
 A) REVISE OVERHANG LENGTH AND HEIGHT. SEE PLANS.
  
 B) MAKE SURE A/C AREA MATCHES PLANS.
  
 C) COMPLETE ALL INFORMATION ON TOP OF FORM.
  
 D) REVISE RAISED WOOD, ADJACENT AREA. SEE PLANS FOR
 CORRECT INFORMATION.
  
 5- PROVIDE COMPLETE INFORMATION FOR STORM SHUTTERS.
 PROVIDE PRODUCT APPROVAL AND COMPLETE INSTALLATION
 SCHEDULE. SEE ATTACHED SAMPLE OF INSTALLATION
 SCHEDULE.
 *** NOTE: DESIGNER OF RECORD TO REVIEW AND APPROVE IN
 WRITING PRODUCT APPROVAL AS REQUIRED BY SEC. 106.3.3
 CITY AMENDMENTS TO FBC 2004.
  
 6- BUILDING VALUATION AND RADON FEES WILL BE UPDATED
 WHEN CORRECT FLOOR AREAS ARE PROVIDED.
  
 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY RULE 9B-72
 FOR:
 A) ENTRY DOOR WITH IMPACT GLASS AS SPECIFIED ON
 PLANS.
  
 B) ASPHALT SHINGLES.NOA #04-0305.03 EXPIRED ON
 02/21/07.
  
 C) SINGLE HUNG WINDOWS. NEED LEGIBLE DRAWINGS.
  
 D) COLONIAL SHUTTERS SHOWN ON EXTERIOR ELEVATIONS.
  
 E) WINDOW MULLIONS. NEED CLEAR AND LEGIBLE
 DRAWINGS.
  
 F) LOUVERS IN GABLE END WALLS.
  
 G) REAR AND 2ND FLOOR FRENCH DOORS.
  
 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 9- ARCHITECT TO PROVIDE ALL HIS INFORMATION AND FIRM'S
 REGISTRATION NUMBERAS REQUIRED BY SEC. 61G1-16.004 OF
 FLORIDA ADMINISTRATIVE CODE.
  
 10- A) PROVIDE SURVEY WITH PROPOSED BUILDING LAYOUT AND
 SETBACKS.
  
 B) SURVEY TO HAVE ORIGINAL SIGNATURE AS REQUIRED BY
 CHAPTER 472 FLORIDA STATUTE.
  
 11- SHEET 2.1:SPECIFY TOP AND BOTTOM CONNECTORS FOR
 4" WOOD COLUMNS. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 12- SHEET 3.1:
 A) REVISE PLYWOOD SHEATHING NAILING SCHEDULEAND
 NOTE REGARDING RING SHANK NAILS. SEE SEC. R803.2.3.1 OF
 2004 FLORIDA RESIDENTIAL CODE.
  
 B) REVISE SKETCHSHOWING ROOF ZONES.SEE FIGURE
 R301.2(8) 2004 FLORIDA RESIDENTIAL CODE.
  
 C) PROVIDE DETAIL C/3.1 SHOWING CONNECTION OF GABLE
 END BEAM WITH STEEL CAP. SEC. 106.1.2 CITY AMENDMENT TO
 FBC 2004.
  
 D) CLARIFY WHY USING ONLY ONE LEDGER TO SUPPORT
 FLOOR TRUSSES. TAKE INTO CONSIDERATION HOW MUCH BEARING
 IS REQUIRED AT THE END OF TRUSSES AND AT THE END OF
 GIRDER TRUSSES. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 E) PROVIDE DETAIL SHOWING CONNECTION OF FRONT PORCH
 WOOD BEAM TO CONTINUOUS STEEL COLUMN AT CORNER AREAS.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 F) SPECIFY HOW LONG ARE THE HILTI EXP.ANCHORS
 SPECIFIED TO SUPPORT 2X8 JOISTS AT FRONT PORCH. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 G) SPECIFY CONNECTORS AT THE ENDS OF 2X8 JOISTS AT
 FRONT PORCH. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 H) WIND DESIGN INFORMATION ITEM #5: CLARIFY WHY THE
 INTERNAL PRESSURE COEFFICIENT IS NOT APPLICABLE IF THIS
 BUILDING IS DESIGNED ASCLOSED?. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 I) CLEARLY SPECIFY DESIGN PRESSURES FOR EACH OPENING
 IN THIS BUILDING. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 13- SHEET 4.1:
 A) SPECIFY SAFETY GLASS FOR WINDOW NEXT TO THE BATH
 TUB IN MASTER BATHROOM AS REQUIRED BY SEC. R308.4 OF
 2004 FLORIDA RESIDENTIAL CODE
  
 B) REVISE ALL AREA CALCULATIONS.
  
 14- SHEET 6.1: REVISE CARDINAL ORIENTATION OF EACH
 ELEVATION.SEE SURVEY FOR CORRECT BUILDING
 ORIENTATION.
  
  
 15- SHEET 7.1 WALL SECTION 2/7.1: CLARIFY TYPE OF ROOF
 COVERING. SHINGLES OR TILE. REVISE AS REQUIRED.
  
 16- SHEET 9.1:
 A) PROVIDE COMPLETE STRUCTURAL BUCK DETAIL FOR ALL
 DOORAND WINDOW TYPES.SEE SEC. R 613.6.2 OF 2004
 FLORIDA RESDIENTIAL CODE FOR PROPERINSTALLATION.
 SPECIFY ALL FASTENERS. ALSO, SEE PRODUCT APPROVALS FOR
 REQUIRED BUCK SIZE.
  
 B) WINDOW F IS NOT AN EGRESS WINDOW. REVISE AS
 REQUIRED.
  
 16- SOIL TEST REPORT TO HAVE ENGINEERING FIRM
 CERTIFICATE OF AUTHORIZATION NUMBER IN ALL SHEETS AS
 REQUIRED BY SEC. 61G15-23.002 FLORIDA ADMINISTRATIVE
 CODE
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712