2007-03-08 17:10:24****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBEXISTING BUILDING CODE 2004
 FBC R RESIDENTIAL 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
  
 1.)THE INSTALLATION SCHEDULE IS TO STATE THE MOUNTING
 CONNECTION TYPE.ON THE PRODUCT APPROVAL, THIS WOULD
 BE ON SHEETS 13 THROUGH 15 AND REFERS TO THE CONNECTION
 DETAIL, NOT THE FASTENER.ANCHOR SPACING IS NOT
 COMPLIANT FOR ALL CONNECTION TYPES.FOR INSTANCE,
 OPENING 7, 10INCH SPACING ON THE BOTTOM, THE CHART
 YOU'VE HIGHLIGHTED FOR CBS REQUIRES 8INCH.
  
 2.)A NOTICE OF COMMENCEMENT MUST BE FILED WITH THE
 CLERK OF COURTS PRIOR TO PERMIT PICKUP.
  