Plan Review Notes For Permit 07011295 |
Permit Number |
07011295 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-01-29 17:26:49 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE | | FBC2004 | | | | 1.)THE ENGINEER STATES THAT THE ASSEMBLY ON PAGE 28 | | WILL BE USED, BUT THE CONTRACTOR SUBMITTED THE ASSEMBLY | | ON PAGES 26-27. | | | | 2.)WHICH OPTION WILL YOU USE?THE DIFFERENT | | FASTENERS HAVE DIFFERENT PRESSURE LIMITATIONS.THE | | ENGINEERING SHOULD ADDRESS WHICH OF THE DIFFERENT | | OPTIONS ON THE APPROVED ASSEMBLY IS TO BE USED. | | |
|