2007-03-13 09:00:39 | BUILDING PLAN REVIEW |
| PERMIT: 07011255 |
| ADD: 700 S. ROSEMARY AVE |
| CONT: VENTURA CONST. |
| TEL: (561)###-#### |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2006 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2)2004 FL. BLD CODE 1603.1.4 THE |
| FOLLOWING INFORMATION RELATED TO WIND |
| SHALL BE SHOWN ON THE CONSTRUCTION |
| DRAWINGS, |
| 1)- BASIC WIND SPEED, MPH |
| 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| CATEGORY |
| 3)- WIND EXPOSURE |
| 4)- INTERNAL PRESSURE COEFFICIENT, |
| 5)- COMPONENTS & CLADDING, THE DESIGN |
| WIND PRESSURES IN TERMS OF PSF. THE DRAWINGS SHALL |
| INDICATE THE 2004 FBC, NOT THE 2003 SBC. |
| |
| 3)THE ENGINEER JAMES WESTBROOK HAS A DELINQUENT |
| STATUS ON THE STATE WEBSITE. THE LICENSE ISSUE HAS TO |
| BE ADDRESSED BEFORE A PERMIT CAN BE ISSUED. ALSO THE |
| ADDRESS ON THE STATE WEBSITE DOES NOT MATCH THE ONE ON |
| THE DRAWINGS.SEE ATTATCHED PRINT OUT FROM DBPR. |
| |
| 4)F.A.C.61G15-23.002(2)ENGINEERES SHALL LEGIBLY |
| INDICATE THEIR NAME, ADDRESS, AND LICENSE NUMBER ONEACH |
| SHEET. IF PRACTICING THROUGH A DULY AUTHORIZED |
| ENGINEERING BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE |
| THEIR NAME AND LICENSE NUMBER, AS WELL AS, THE NAME |
| ADDRESS, AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE |
| ENGINEERING BUSINESS ON EACH SHEET. A TITLE BLOCK ON |
| EACH SHEET CONTAINING THE PRINTED NAME, ADDRESS, AND |
| LICENSE NUMBER OF THE ENGINEER OR IF APPLICABLE, THE |
| NAME AND LICENSE NUMBER OF THE ENGINEER, AND THE NAME, |
| ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE |
| ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT. |
| THIS INFORMATION IS MISSING ON THE PLANS. |
| |
| 5)2004 FBC PAGE 35.23R REFERENCES THE RCSC-88. THE |
| PLANS INDICATE RCSC-2000. PROVIDE THE CODE SECTION |
| WHICH REFERS TO RCSC-2000. |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |
| 805-6726 |
| |
| |
| |
| |