2007-02-01 17:06:58BUILDING PLAN REVIEW
 PERMIT:07011255
 ADD: 700 S. ROSEMARY AVE
 CONT: VENTURA ARCHITECTURE & DEV.
 TEL: (561)856-6655
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)THE ADDRESS ON THE DRAWINGS HAS AN NEW YORK
 ADDRESS. SHOW THE CORRECT FLORIDA ADDRESS FOR THIS
 PROJECT ON DRAWINGS. SEE ALL SHEETS.
  
 4)THE CURRENT BULDING CODE WHIC IS USED HERE IN THE
 CITY OF WEST PALM BEACH IS THE 2004 FLORIDA BUILDING
 CODE. THE ACI-318-99, HAS BEEN CHANGED TO ACI-318-02
 SEE FBC CH.35. THE LETTER SUMMARIXING THE STRUCTURAL
 ANALYSIS FOR THE EXISTING TWO STORY STEEL FRAME
 BUILDING NEEDS REVISING TO SHOW THE CORRECT CODE AND
 CODE SECTIONS.
  
 5) 1509.3 TANKS.
 TANKS HAVING A CAPACITY OF MORE THAN 500 GALLONS (2 M 3
 ) PLACED IN OR ON A BUILDING SHALL BE SUPPORTED ON
 MASONRY, REINFORCED CONCRETE, STEEL OR TYPE IV
 CONSTRUCTION PROVIDED THAT, WHERE SUCH SUPPORTS ARE
 LOCATED IN THE BUILDING ABOVE THE LOWEST STORY, THE
 SUPPORT SHALL BE FIRE-RESISTANCE RATED AS REQUIRED FOR
 TYPE IA CONSTRUCTION.
  
 6)THE SIGNATURESON ONE SET OF THE DRAWINGS ARE
 STAMPED. THE SIGNATURE OF BOTH SETS ARE DIFFERENT,
 HOWEVER THE NAME AND SEAL IS THE SAME ON BOTH SETS OF
 DRAWINGS. SUCH SIGNATURE, DATE, AND SEAL SHALL BE
 EVIDENCE OF THE AUTHENTICITY. FLORIDA STATUTES
 471.025.
 F.A.C. 61G15-23.002ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ADDRESS AND LICENSE NUMBER ON EACH SHEET.
 IF PRACTICING THROUGH A DULYY AUTHORIZE ENGINEERING
 BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME
 AND LICENSE NUMBER, AS WELL AS, THE NAME, ADDRESS, AND
 CERTIFICATE OF AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK ON EACH SHEET
 CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE
 NUMBER OF THE ENGINEER OR IF APPLICABLE,
  
 7) THE FLORIDA BOARD OF PROFESSIONAL ENGINEERS AMENDED
 ITS SEALS RULE EFFECTIVE FEBRUARY 5, 2004. THEY CLEANED
 UP THE APPERANCE OF THE SEAL BY ELIMINATING OBSOLETE
 CONTENT AND CHANGING THE WORD "CERTIFICATE" TO
 "LICENSE". SEE F.A.C. 61G15-23.001(1) FOR MORE
 INFORMATION ON THE NEW SEALS.
  
 8)DID THE STRUCTURAL ENGINEER TAKE INTO CONSIDERATION
 THE WEIGHT OF BOTH TANKS BEING ON THE ROOF AT THE SAME
 TIME?THE ANALYSIS PROVIDED IS FOR THE 25000 LBS NEW
 CHILLER. WHAT ABOUT THE EXISTING CHILLER? THE WEIGHT OF
 BOTH CHILLER SHALL BE TAKEN INTO CONSIDERATION SINCE
 THEY WILL BE ON THE ROOF AT THE SAME TIME.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER