2007-02-03 08:30:14BUILDING PLAN REVIEW
 PERMIT:
 ADD:
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)THE LETTER FROM THE ENGINEER IS NOT WHAT THE NOA
 REQUIRES. THE NOA STATE CLEARLY "CALCULATIONS PREPARED,
 SIGNED AND SEALED BYA FLORIDA REGISTERED PROFESSIONAL
 ENGENEER, ARCHITECT, OR ROOF CONSULTANT. PROVIDE THE
 CALCULATIONS FROM THE ENGINEER WHICH WILL MEET THE
 REQUIRED UPLIFT PRESSURES AS CALCULATED BY THE
 ENGINEER. THE CALCULATIONS SHALL THE PRESSURE
 CALCULATED FOR ZONES 1 / 2 AND 3. USING THE NOA
 SUBMITTED.SEE (RAS) NO. 117 FOR MORE INFORMATION.
  
 ROOFING PERMIT; ONLY CHECKED ITEMS APPLY
  
 _OK___1.)A NOTICE OF COMMENCEMENT MUST BE FILED
 WITH THE CLERK OF COURTS PRIOR TO PERMIT PICKUP,
 FS713.13.
  
 __OK__2.)CONTRACTOR IS TO PROVIDE THE FOLLOWING
 INFORMATION ON THE APPLICATION, SEE ATTACHED
 POLICY:MEAN ROOF HEIGHT/ ROOF PITCH / ROOF DECK TYPE /
 AREA OF EACH ROOF TYPE
  
 ____3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED IN ADDITION TO THE EVALUATION REPORT
 SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG
  
 _OK__4.)FOR THE FLAT DECK, SELECT THE APPROVED
 ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER
 IF THE OPTIONS HAVE DIFFERENT PRESSURE LIMITATIONS.
  
 _XX___5.)FOR THE FLAT DECK, SPECIFY THE ENHANCED
 FASTENING FOR CORNER AND PERIMETER ZONES.
  
 _XX___ 6)SEE PRODUCT LIMITATION #7.CALCULATIONS
 PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF
 CONSULTANT REQUIRED FOR ENHANCED FASTENING.
  