2007-02-03 08:30:14 | BUILDING PLAN REVIEW |
| PERMIT: |
| ADD: |
| CONT: |
| TEL: (561)###-#### |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2006 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW |
| ACTION: DENIED |
| |
| 1)THE LETTER FROM THE ENGINEER IS NOT WHAT THE NOA |
| REQUIRES. THE NOA STATE CLEARLY "CALCULATIONS PREPARED, |
| SIGNED AND SEALED BYA FLORIDA REGISTERED PROFESSIONAL |
| ENGENEER, ARCHITECT, OR ROOF CONSULTANT. PROVIDE THE |
| CALCULATIONS FROM THE ENGINEER WHICH WILL MEET THE |
| REQUIRED UPLIFT PRESSURES AS CALCULATED BY THE |
| ENGINEER. THE CALCULATIONS SHALL THE PRESSURE |
| CALCULATED FOR ZONES 1 / 2 AND 3. USING THE NOA |
| SUBMITTED.SEE (RAS) NO. 117 FOR MORE INFORMATION. |
| |
| ROOFING PERMIT; ONLY CHECKED ITEMS APPLY |
| |
| _OK___1.)A NOTICE OF COMMENCEMENT MUST BE FILED |
| WITH THE CLERK OF COURTS PRIOR TO PERMIT PICKUP, |
| FS713.13. |
| |
| __OK__2.)CONTRACTOR IS TO PROVIDE THE FOLLOWING |
| INFORMATION ON THE APPLICATION, SEE ATTACHED |
| POLICY:MEAN ROOF HEIGHT/ ROOF PITCH / ROOF DECK TYPE / |
| AREA OF EACH ROOF TYPE |
| |
| ____3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| REQUIRED IN ADDITION TO THE EVALUATION REPORT |
| SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG |
| |
| _OK__4.)FOR THE FLAT DECK, SELECT THE APPROVED |
| ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER |
| IF THE OPTIONS HAVE DIFFERENT PRESSURE LIMITATIONS. |
| |
| _XX___5.)FOR THE FLAT DECK, SPECIFY THE ENHANCED |
| FASTENING FOR CORNER AND PERIMETER ZONES. |
| |
| _XX___ 6)SEE PRODUCT LIMITATION #7.CALCULATIONS |
| PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF |
| CONSULTANT REQUIRED FOR ENHANCED FASTENING. |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |