Plan Review Notes
Plan Review Notes For Permit 07011242
Permit Number 07011242
Review Stop B
Sequence Number 1
Notes
Date Text
2007-02-09 14:33:20****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBEXISTING BUILDING CODE 2004
 FBC R RESIDENTIAL 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
 1.)THE INSTALLATION SCHEDULE GIVES 141.5 AS OPENING
 HEIGHT FOR OPENING 1, SPAN OF 75. INDUSTRY STANDARD AND
 THE FORM IS W X H.IT APPEARS THAT THE OPEINGS ARE
 BACKWARDS?
  
 2.)DEPENDING ON THE CONNECTION DETAIL, THE SPAN IS
 USUALLY LARGER THAN THE OPENING HEIGHT.YOU HAVE
 INDICATED THE SHUTTER SPAN AS THE SAME AS THE OPENING
 WIDTH.IF THE WIDTH IS ACTUALLY THE HEIGHT, THE SPAN
 STILL APPEAR INCORRECT.
  
 3.)PLEASE REVISE THE INSTALLATION SCHEDULE AND CHECK
 ALL ANCHORING.ANCHORING WAS NOT REVIEWED AS SPANS
 HAVE NOT BEEN DETERMINED.
  