2007-04-12 16:47:53 | ** UNSAT ** |
| |
| 1) NOTE: PLEASE SEE THE NEW REVISED ENERGY CALCULATIONS |
| ARE NOT SEALED BY THE ENGINEER OF RECORD AS REQUIRED |
| PER 13-103.1.1.1 |
| PLEASE SUBMIT SIGNED, DATED AND SEALED. FS 471.025 |
| |
| 2) NOTE: PLEASE SEE THE NUMBER OF*B* FIXTURES ON |
| PLANS DO NOT CORRELATE WITH THE NUMBER OFFIXTURES ON |
| ENERGY CALCULATIONS.PLEASE SEE THE NUMBER OF *A* |
| FIXTURES ALSO DO NOT CORRELATE. THESE SEEM TO BE |
| REVERSED. PLEASE SEE THE WATTAGE ON *C* ARE 25 ON |
| ENERGY CALCULATIONS AND AS 26 ON PLANS. |
| PLEASE ADJUST PLANS, OR ENERGY CALCULATIONS. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |