2007-02-03 11:32:38DENIED;
 1. SEE ELECTRICAL PLAN REVIEW NOTES #1 AND #2.
 2. SPACE ABOVE THE DROPPED CEILING IS A PLENUM PER
 MECHANICAL PAGE M2.1, REVISE PLUMBING NOTE#11 ON PAGE
 P0.1. PVC CANNOT BE USED. EXCEPTABLE MATERIAL WOULD BE
 CAST IRON OR COPPER.
 3. WATER HAMMER ARRESTORS ARE REQUIRED ON THE HOT AND
 COLD WATER PER SECTION 604.9, AND PER MANUFACTURE'S
 INSTALLATION INSTRUCTIONS, AS CLOSE TO THE FIXTURE AS
 POSSIBLE. (ONE RISER DIAGRAM MARKED IN RED)
 4.SHOW CLEAR FLOOR SPACE, FRONTAL APPROACH, ON FLOOR
 PLAN AT BREAK SINK.
 5.PAGE A-08(2)DOES NOT CLEARLY SHOW THE FRONTAL
 APPROACH OR MEASUREMENTS ,WIDTH/ AND HIGHT ON TOP OF
 SINK.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695