Plan Review Notes
Plan Review Notes For Permit 07011233
Permit Number 07011233
Review Stop M
Sequence Number 1
Notes
Date Text
2007-02-01 09:32:02*** DENIED ***
 1) SEE ELECTRICAL REVIEW NOTES #1 AND 2, PLEASE
 CORRECT.
  
 2)PAGES A-05, A-07 AND A-08 SHOW THE SPACE ABOVE THE
 ACCOUSTIC TILE CEILING TO BE AN OPEN PLENUM AND WOULD
 NOT REQUIRE RETURN AIR TRANSFER DUCTS, IF THIS IS SO
 PLEASE DO NOT SHOW RETURN AIR TRANSFER DUCTS ON PAGE
 M-2.1. IF NOT AN OPEN PLENUM RETURN AIR TRANSFER DUCTS
 ARE UNDER-SIZED. BALANCED RETURN AIR MAY BE ACHIEVED
 BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE. PER 2004 FBC/M 601.4. PLEASE
 CORRECT.
  
 3) IF NOT AN OPEN PLENUM PROVIDE RETURN AIR TEANSFER
 DUCTS TO THE WATING ROOM AND SMALL CONFERENCE ROOM.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.