Plan Review Notes For Permit 07011233 |
Permit Number |
07011233 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-02-01 09:32:02 | *** DENIED *** | | 1) SEE ELECTRICAL REVIEW NOTES #1 AND 2, PLEASE | | CORRECT. | | | | 2)PAGES A-05, A-07 AND A-08 SHOW THE SPACE ABOVE THE | | ACCOUSTIC TILE CEILING TO BE AN OPEN PLENUM AND WOULD | | NOT REQUIRE RETURN AIR TRANSFER DUCTS, IF THIS IS SO | | PLEASE DO NOT SHOW RETURN AIR TRANSFER DUCTS ON PAGE | | M-2.1. IF NOT AN OPEN PLENUM RETURN AIR TRANSFER DUCTS | | ARE UNDER-SIZED. BALANCED RETURN AIR MAY BE ACHIEVED | | BY. | | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY | | INCREASING THE RETURN TRANSFER ONE AND | | ONE HALF TIMES THE CROSS SECTIONAL AREA | | (SQUARE INCHES) OF THE SUPPLY DUCT | | ENTERING THE ROOM OR SPACE IT'S SERVING | | AND THE DOOR HAVING AT LEAST AN | | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE | | PROPER RETURN AIR BALANCE. PER 2004 FBC/M 601.4. PLEASE | | CORRECT. | | | | 3) IF NOT AN OPEN PLENUM PROVIDE RETURN AIR TEANSFER | | DUCTS TO THE WATING ROOM AND SMALL CONFERENCE ROOM. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|