Plan Review Notes For Permit 07011232
Permit Number 07011232
Review Stop P
Sequence Number 1
Notes
Date Text
2007-02-03 11:54:331. SEE ELECTRICAL PLAN REVIEW NOTES #1AND # 2.
 2. CHANGE NOTE 11, PLUMBING NOTES, PAGE P0.1. PVC
 CANNOT BE USED FOR THIS INSTALLATION. ABOVE THE DROPPED
 CEILING IS A PLENUM.
 3. WATER HAMMER ARRESTORS TO BE INSTALLED PER
 MANUFACTURE'S INSTALLATION INSTRUCTIONS. AS CLOSE TO
 THE FIXTURE AS POSSIBLE. ONE WATER RISER MARKED IN
 RED.
 PLUMBING PLAN REVIEW BY;