Plan Review Notes For Permit 07011232 |
Permit Number |
07011232 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-02-01 10:14:26 | *** DENIED *** | | 1) SEE ELECTRICAL REVIEW NOTES 1 AND 2, PLEASE | | CORRECT. | | | | 2) RETURN AIR TRANSFER DUCTS TO CONFERENCE ROOM, OFFICE | | #2 AND #4 ARE UNDER SIZED. BALANCED RETURN AIR MAY BE | | ACHIEVED BY. | | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY | | INCREASING THE RETURN TRANSFER ONE AND | | ONE HALF TIMES THE CROSS SECTIONAL AREA | | (SQUARE INCHES) OF THE SUPPLY DUCT | | ENTERING THE ROOM OR SPACE IT'S SERVING | | AND THE DOOR HAVING AT LEAST AN | | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE | | PROPER RETURN AIR BALANCE. | | PER 2004 FBC/M 601.4. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. | | |
|