2007-02-06 12:12:44 | *****DENIED***** |
| |
| |
| 01.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE |
| PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED. |
| |
| 02. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| |
| 03.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS |
| SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT |
| OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. |
| |
| 04.THE COMPLETE ADDRESS OF WHERE THE SCOPE OF WORK |
| WILL BE CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH |
| SUBMITTED PLAN SHEET. |
| |
| 05.DISPLAY THE TENANT SPACE NUMBER FOR THIS SITE SO |
| THAT IT IS DISTINGUISHABLE FROM OTHER TENANT SITES ON |
| THE FLOOR.AS PER WEST PALM BEACH CODE, THOSE NUMBERS |
| SHALL BE NO LESS THAN 3" IN HEIGHT. |
| |
| 06.ON SHEET A-03 (4TH FLOOR PLAN) AND SHEET A-04 (4TH |
| FLOOR REFLECTED CEILING PLAN) REFERS TO SUITE 430. WHAT |
| IS THE CORRECT SUITE NUMBER? |
| |
| 07.DOOR(S) LEADING DIRECTLY TO THE FOURTH FLOOR |
| CORRIDOR SHALL BE AN APPROVED, LISTED, AND LABELED FIRE |
| DOOR & ASSEMBLY IN ACCORDANCE WITH THE REQUIREMENTS OF |
| NFPA 80. |
| |
| 08.WHAT IS INTERIOR FINISH CLASSIFICATION FOR THE |
| WALLS AND CEILINGS IN THE EXITS, EXIT ACCESS CORRIDORS, |
| AND IN ALL OTHER AREAS? |
| |
| 09.PROVIDE A LIFE SAFETY PLAN SHEET WHICH INDICATES |
| THE TRAVEL DISTANCE TO THE EXIT(S).ALSO ON THIS |
| SHEET, INDICATE THE LOCATION OFFIRE EXTINGUISHER(S) |
| AT DISTANCES TO SATISFY THE 75' TRAVEL DISTANCE |
| REQUIREMENT. |
| |
| 10.ON SHEET FA0.1, FIRE ALARM NOTE #17 SHOULD BE |
| CHANGED TO "INITIATE A GENERAL FIRE ALARM". |
| |
| 11.PROVIDE A LAYOUT OF THE FIRE SPRINKLER SYSTEM FOR |
| THIS TENANT SPACE. |
| |
| |
| |
| |
| TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, |
| INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH |
| ITEM WAS ADDRESSED ON THE PLAN. |
| |
| |