2007-01-31 07:39:54 | ** UNSAT ** |
| |
| |
| 1) NOTE: PLEASE SEE MISSING ADDRESS INFORMATION FROM |
| TITLE BLOCKS. PLEASE SEE THE SUITE/UNIT NUMBER IS BEING |
| SHOWN, HOWEVER NOT THE ADDRESS/ LOCATION. THIS IS 444 |
| RAILROAD AVE IN OUR SYSTEM AND THAT WHICH IS BEING |
| APPLIED FOR. |
| FAC 61G1-16.004, FAC61G15-23.002 |
| |
| 2) NOTE: PLEASE SEE MISSING COMPLETE INFORMATION FOR A |
| TITLE BLOCK FOR THE ARCHITECT OF RECORD. PLEASE SEE |
| ATTACHED SHEET FROM DEPARTMENT OF BUSINESS AND |
| PROFESSIONAL REGULATION. PLEASE SEE NO ADDRESS |
| INFORMATION ETC. |
| PLEASE KNOW IF WORKING THROUGH PBM DEVELOPMENT, AND PBM |
| IS OFFERING ARCHITECTURAL SERVICES, THEN PBM WOULD BE |
| REQUIRED TO LIST THEIR CERTIFICATE OF AUTHORIZATION |
| NUMBER. (THIS HAS ALREADY BEEN GONE OVER WITH STAFF |
| FROM PBM AND IT IS OUR UNDERSTANDING THAT APPLICATION |
| TO THE DEPARTMENT OF BUSINESS AND PROFESSIONAL |
| REGULATIONS HAS/IS TAKING OR TAKEN PLACE. |
| PLEASE KNOW IF PERMIT ISSUANCE IS DOWN TO ONLY THIS |
| COMMENT AND THE CERTIFICATE OF AUTHORIZATION NUMBER HAS |
| NOT YET BEEN ISSUED FROM THE STATE, THE TITLE BLOCKS |
| WOULD BE REQUIRED TO BE REVISED TO BE LISTED WITH THE |
| ARCHITECT ONLY. APPLICATION MADE TO THE STATE DOES NOT |
| CONSTITUTE THE LICENSE BEING ISSUED AND THE COMPANY |
| OFFERING ARCHITECTURAL SERVICES IS NOT PERMITTED. AS |
| THIS COMMENT HAS BEEN MADE ON SEVERAL OCCASIONS, |
| CONTACT WITH THE STATE BOARD OF ARCHITECT'S LEGAL |
| COUNSEL MAY BE REQUIRED. |
| FLORIDA ADMINISTRATIVE CODE 61G1-16.004, FLORIDA |
| STATUTES 481.219 |
| **THIS IS NOT A COMMENT RELATED TO KAMM CONSULTING, |
| HOWEVER TITLE BLOCKS ARE REQUIRED FOR ALL SHEETS PER |
| ABOVE AND WHETHER OR NOT COMMENT IS MADE BY ANY OTHER |
| TRADE. |
| |
| 3) NOTE: PLEASE LIST THE FOLLOWING MINIMUM CODES |
| RELEVANT TO THIS PROJECT AND DESIGN. |
| 2002 NFPA-72, 2005 NFPA-70, 2003 NFPA-101 |
| PLEASE SEE AS THE PERMIT WAS APPLIED FOR ON OR AFTER |
| DECEMBER 8TH, 2006 THE 2006 REVISIONS TO THE 2004 FBC |
| AND THE 2005 NATIONAL ELECTRICAL CODE WAS ADOPTED BY |
| THE STATE OF FLORIDA. |
| PLEASE ADJUST CODES ON PLANS. |
| |
| 4) NOTE: PLEASE SEE MISSING LIGHTING CONTROL FOR ALL |
| PER 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE SEE |
| MISSING CONTROLS FOR COMMON AREAS AND STORAGE AREAS. |
| PLEASE SEE THE COMMON AREA HALLWAY MUST CONTAIN A |
| DEVICE(S) WHICH PROVIDE SUFFICIENT COVERAGE. PLEASE SEE |
| OVER RIDES DEVICES FOR THESE AREAS ALSO DEPENDING ON |
| "SYSTEM" OR DEVICES CHOSEN. PLEASE SEE THE SYMBOL |
| LEGEND FOR ALL DEVICES SHALL INDICATE ALL MAXIMUM TIMES |
| FOR DEVICES. (30MINS FOR OCCUPANCY SENSOR TYPE AND 4HRS |
| MAX FOR TIMER TYPE) |
| PLEASE PROVIDE SCHEDULING FOR ANY PROPOSED SYSTEM. |
| PLEASE SEE ALL AREAS CONTAIN FLOOR TO CEILING HEIGHT |
| PARTITIONS SHALL CONTAIN DEVICE(S) FOR CONTROL. (PLEASE |
| SEE STORAGE) |
| PLEASE SEE 13-415.2, 13-415.2.ABC.1 FOR MISSING MAXIMUM |
| PERMITTED LIGHTING POWER DENSITIES. |
| PLEASE ALSO SEE 13-415.AB.1 FOR MISSING ENERGY |
| CALCULATIONS REQUIRED FOR NEW TENANT BUILD-OUT. |
| ** PLEASE SUBMIT THE ABOVE. AS THERE ARE ITEMS NOT YET |
| SUBMITTED, A REVIEW OF SAID SYSTEM/DEVICES ETC CAN NOT |
| BE FULLY ACCOMPLISHED AT THIS TIME. |
| |
| 5) NOTE: PLEASE PROVIDE A DETAIL ON ALL EMERGENCY |
| AND/OR EXIT LIGHTING WIRED AHEAD OF ANY OVER RIDE |
| CONTROL DEVICES PER 700.12E. PLEASE SEE A |
| CLOUDED/HIGHLIGHTED NOTE MAY ALSO BE DONE. THIS AHJ HAS |
| BEEN HAVING MANY INSTANCES WHERE EMERGENCY AND EXIT |
| LIGHTS ARE BEING WIRED ON THE LOAD SIDE OF OC/ TIMER |
| DEVICES. |
| |
| 6) NOTE: PLEASE INDICATE ALL CONTINUOUS LOADS AT 125%. |
| 215.3, 230.42 ETC. |
| FBC 106.1.2 ADMIN SECTION. |
| |
| 7) NOTE: PLEASE KNOW EITHER AT THIS POINT OR BEFORE |
| FINAL, A REVISION FOR ALL CIRCUITS TO SPECIFIC ROOMS |
| AND AREAS WILL BE REQUIRED. (LIGHTING CIRCUITS ETC.) |
| 408.4. |
| ALL RECEPTACLE CIRCUITS ARE OK AS SHOWN. SEE EXCERPT |
| FROM NEC HANDBOOK. |
| *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| SECTION.* |
| |
| 8) NOTE: PLEASE CLARIFY HOW THE PANEL SCHEDULE(S) |
| INDICATE ALL THE CIRCUITS AS EXISTING FOR ALL THESE |
| SPACES WHICH HAVE YET TO BE PERMITTED. PLEASE INDICATE |
| NEW CIRCUITING AND WHAT?S EXISTING. PLEASE SEE THAT NO |
| OTHER TENANT BUILD OUTS HAVE BEEN PERMITTED AT THIS |
| TIME. |
| |
| 9) NOTE:** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDEDSHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS.PLEASE KNOW ONLY |
| ONE SET OF THE OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |