Plan Review Notes
Plan Review Notes For Permit 07011232
Permit Number 07011232
Review Stop E
Sequence Number 1
Notes
Date Text
2007-01-31 07:39:54** UNSAT **
  
  
 1) NOTE: PLEASE SEE MISSING ADDRESS INFORMATION FROM
 TITLE BLOCKS. PLEASE SEE THE SUITE/UNIT NUMBER IS BEING
 SHOWN, HOWEVER NOT THE ADDRESS/ LOCATION. THIS IS 444
 RAILROAD AVE IN OUR SYSTEM AND THAT WHICH IS BEING
 APPLIED FOR.
 FAC 61G1-16.004, FAC61G15-23.002
  
 2) NOTE: PLEASE SEE MISSING COMPLETE INFORMATION FOR A
 TITLE BLOCK FOR THE ARCHITECT OF RECORD. PLEASE SEE
 ATTACHED SHEET FROM DEPARTMENT OF BUSINESS AND
 PROFESSIONAL REGULATION. PLEASE SEE NO ADDRESS
 INFORMATION ETC.
 PLEASE KNOW IF WORKING THROUGH PBM DEVELOPMENT, AND PBM
 IS OFFERING ARCHITECTURAL SERVICES, THEN PBM WOULD BE
 REQUIRED TO LIST THEIR CERTIFICATE OF AUTHORIZATION
 NUMBER. (THIS HAS ALREADY BEEN GONE OVER WITH STAFF
 FROM PBM AND IT IS OUR UNDERSTANDING THAT APPLICATION
 TO THE DEPARTMENT OF BUSINESS AND PROFESSIONAL
 REGULATIONS HAS/IS TAKING OR TAKEN PLACE.
 PLEASE KNOW IF PERMIT ISSUANCE IS DOWN TO ONLY THIS
 COMMENT AND THE CERTIFICATE OF AUTHORIZATION NUMBER HAS
 NOT YET BEEN ISSUED FROM THE STATE, THE TITLE BLOCKS
 WOULD BE REQUIRED TO BE REVISED TO BE LISTED WITH THE
 ARCHITECT ONLY. APPLICATION MADE TO THE STATE DOES NOT
 CONSTITUTE THE LICENSE BEING ISSUED AND THE COMPANY
 OFFERING ARCHITECTURAL SERVICES IS NOT PERMITTED. AS
 THIS COMMENT HAS BEEN MADE ON SEVERAL OCCASIONS,
 CONTACT WITH THE STATE BOARD OF ARCHITECT'S LEGAL
 COUNSEL MAY BE REQUIRED.
 FLORIDA ADMINISTRATIVE CODE 61G1-16.004, FLORIDA
 STATUTES 481.219
 **THIS IS NOT A COMMENT RELATED TO KAMM CONSULTING,
 HOWEVER TITLE BLOCKS ARE REQUIRED FOR ALL SHEETS PER
 ABOVE AND WHETHER OR NOT COMMENT IS MADE BY ANY OTHER
 TRADE.
  
 3) NOTE: PLEASE LIST THE FOLLOWING MINIMUM CODES
 RELEVANT TO THIS PROJECT AND DESIGN.
 2002 NFPA-72, 2005 NFPA-70, 2003 NFPA-101
 PLEASE SEE AS THE PERMIT WAS APPLIED FOR ON OR AFTER
 DECEMBER 8TH, 2006 THE 2006 REVISIONS TO THE 2004 FBC
 AND THE 2005 NATIONAL ELECTRICAL CODE WAS ADOPTED BY
 THE STATE OF FLORIDA.
 PLEASE ADJUST CODES ON PLANS.
  
 4) NOTE: PLEASE SEE MISSING LIGHTING CONTROL FOR ALL
 PER 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE SEE
 MISSING CONTROLS FOR COMMON AREAS AND STORAGE AREAS.
 PLEASE SEE THE COMMON AREA HALLWAY MUST CONTAIN A
 DEVICE(S) WHICH PROVIDE SUFFICIENT COVERAGE. PLEASE SEE
 OVER RIDES DEVICES FOR THESE AREAS ALSO DEPENDING ON
 "SYSTEM" OR DEVICES CHOSEN. PLEASE SEE THE SYMBOL
 LEGEND FOR ALL DEVICES SHALL INDICATE ALL MAXIMUM TIMES
 FOR DEVICES. (30MINS FOR OCCUPANCY SENSOR TYPE AND 4HRS
 MAX FOR TIMER TYPE)
 PLEASE PROVIDE SCHEDULING FOR ANY PROPOSED SYSTEM.
 PLEASE SEE ALL AREAS CONTAIN FLOOR TO CEILING HEIGHT
 PARTITIONS SHALL CONTAIN DEVICE(S) FOR CONTROL. (PLEASE
 SEE STORAGE)
 PLEASE SEE 13-415.2, 13-415.2.ABC.1 FOR MISSING MAXIMUM
 PERMITTED LIGHTING POWER DENSITIES.
 PLEASE ALSO SEE 13-415.AB.1 FOR MISSING ENERGY
 CALCULATIONS REQUIRED FOR NEW TENANT BUILD-OUT.
 ** PLEASE SUBMIT THE ABOVE. AS THERE ARE ITEMS NOT YET
 SUBMITTED, A REVIEW OF SAID SYSTEM/DEVICES ETC CAN NOT
 BE FULLY ACCOMPLISHED AT THIS TIME.
  
 5) NOTE: PLEASE PROVIDE A DETAIL ON ALL EMERGENCY
 AND/OR EXIT LIGHTING WIRED AHEAD OF ANY OVER RIDE
 CONTROL DEVICES PER 700.12E. PLEASE SEE A
 CLOUDED/HIGHLIGHTED NOTE MAY ALSO BE DONE. THIS AHJ HAS
 BEEN HAVING MANY INSTANCES WHERE EMERGENCY AND EXIT
 LIGHTS ARE BEING WIRED ON THE LOAD SIDE OF OC/ TIMER
 DEVICES.
  
 6) NOTE: PLEASE INDICATE ALL CONTINUOUS LOADS AT 125%.
 215.3, 230.42 ETC.
 FBC 106.1.2 ADMIN SECTION.
  
 7) NOTE: PLEASE KNOW EITHER AT THIS POINT OR BEFORE
 FINAL, A REVISION FOR ALL CIRCUITS TO SPECIFIC ROOMS
 AND AREAS WILL BE REQUIRED. (LIGHTING CIRCUITS ETC.)
 408.4.
 ALL RECEPTACLE CIRCUITS ARE OK AS SHOWN. SEE EXCERPT
 FROM NEC HANDBOOK.
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
  
 8) NOTE: PLEASE CLARIFY HOW THE PANEL SCHEDULE(S)
 INDICATE ALL THE CIRCUITS AS EXISTING FOR ALL THESE
 SPACES WHICH HAVE YET TO BE PERMITTED. PLEASE INDICATE
 NEW CIRCUITING AND WHAT?S EXISTING. PLEASE SEE THAT NO
 OTHER TENANT BUILD OUTS HAVE BEEN PERMITTED AT THIS
 TIME.
  
 9) NOTE:** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDEDSHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.PLEASE KNOW ONLY
 ONE SET OF THE OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  