Plan Review Notes For Permit 07011231 |
Permit Number |
07011231 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-02-13 16:49:53 | *****DENIED***** | | | | | | | | 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 2.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL | | BE REMOVED FORM THE SITE AT THE END OF EACH SHIFT OR | | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | 3.WHAT IS THE INTERIOR FINISH CLASSIFICATION FOR THE | | WALLS AND CEILINGS IN THE EXITS, EXIT ACCESS CORRIDORS, | | AND IN ALL OTHER SPACES? | | | | 4.PROVIDE A LIFE SAFETY PLAN SHEET WHICH INDICATES | | THE TRAVEL DISTANCE TO THE EXIT(S).ALSO ON THIS | | SHEET, INDICATE EXIT LIGHTS, EMERGENCY LIGHTS, AND FIRE | | EXTINGUISHER(S).FIRE EXTINGUSHERS SHALL SATISFY THE | | 75' TRAVEL DISTANCE REQUIREMENT. | | | | 5.PROVIDE A LAYOUT OF THE FIRE ALARM SYSTEM FOR THIS | | STRUCTURE.IF THE FIRE ALARM SYSTEM IS MODIFIED DUE TO | | THE SCOPE OF WORK, SEPARATE PLANS AND PERMIT WILL BE | | REQUIRED. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|