Plan Review Notes For Permit 07011231 |
Permit Number |
07011231 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-02-05 09:16:54 | | | | | DENIED/INCOMPLETE INFORMATION. | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | 1} PLEASE INDICATE THE AMPERAGE RATING OF THE MAIN | | BREAKER FOR PANEL "1LA". | | | | 2} CIRCUIT 1LA-7 IS A DESIGNATED FOR LIGHTING ON SHEET | | E-1.01, BUT LISTED AS PART OF A WATER HEATER CIRCUIT ON | | THE PANEL SCHEDULE, SHEET E-2.02, PLEASE CORRELATE. | | | | 3} SUBMIT PANEL SCHEDULES FOR "1LB", "2LA" AND "2LB". | | INCLUDE THE RATINGS OF SAME. | | | | 4} LIGHTING CIRCUIT "1LA-5" SHEET E-1.01, IS LISTED AS | | A AHU CIRCUIT ON THE SCHEDULE, SHEET E2.01. PLEASE | | CORRECT CIRCUIT NUMBER. | | | | 5} PER NOTE #1 SHEET E-1.02, LOCATE THE FIRE ALARM | | ANNUNCIATOR ON THE PLAN. | | | | AN ELECTRICAL PERMIT IS REQUIRED PER 105.1 FBC AS | | AMMENDED. | | PLEASE REMOVE OLD SHEETS, INSERT NEW | | ONES, SUBMIT OLD SHEETS TO EXPEDITE | | REVIEW AND SUBMIT WRITTEN RESPONSE TO | | THE COMMENTS MADE IN THIS REVIEW. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW. | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|