Plan Review Notes
Plan Review Notes For Permit 07011231
Permit Number 07011231
Review Stop E
Sequence Number 1
Notes
Date Text
2007-02-05 09:16:54 
  
 DENIED/INCOMPLETE INFORMATION.
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PLEASE INDICATE THE AMPERAGE RATING OF THE MAIN
 BREAKER FOR PANEL "1LA".
  
 2} CIRCUIT 1LA-7 IS A DESIGNATED FOR LIGHTING ON SHEET
 E-1.01, BUT LISTED AS PART OF A WATER HEATER CIRCUIT ON
 THE PANEL SCHEDULE, SHEET E-2.02, PLEASE CORRELATE.
  
 3} SUBMIT PANEL SCHEDULES FOR "1LB", "2LA" AND "2LB".
 INCLUDE THE RATINGS OF SAME.
  
 4} LIGHTING CIRCUIT "1LA-5" SHEET E-1.01, IS LISTED AS
 A AHU CIRCUIT ON THE SCHEDULE, SHEET E2.01. PLEASE
 CORRECT CIRCUIT NUMBER.
  
 5} PER NOTE #1 SHEET E-1.02, LOCATE THE FIRE ALARM
 ANNUNCIATOR ON THE PLAN.
  
 AN ELECTRICAL PERMIT IS REQUIRED PER 105.1 FBC AS
 AMMENDED.
 PLEASE REMOVE OLD SHEETS, INSERT NEW
 ONES, SUBMIT OLD SHEETS TO EXPEDITE
 REVIEW AND SUBMIT WRITTEN RESPONSE TO
 THE COMMENTS MADE IN THIS REVIEW.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]