2008-02-16 08:43:14 | REVIEW #: 4TH |
| ACTION: FAILED/PENDING |
| |
| FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC |
| CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| |
| THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN |
| RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| |
| 1. NEW FOR 400A HAS BEEN SUBMITTED. HOWEVER, THE INPUT |
| DATA REPORT WAS NOT INCLUDED WITH THE COMPLIANCE FORM |
| AS REQUIRED. PAGE 2 OF THE COMPLIANCE REPORT STATES |
| "IMPORTANT NOTICE: AN INPUT REPORT OF THIS DESIGN |
| BUILDING MUST BE SUBMITTED ALONG WITH THIS COMPLIANCE |
| REPORT." |
| ADDITIONALLY, THE METHOD A COMPLIANCE FORM IS FOR THE |
| "WHOLE BUILDING" INCLUDING ALL MAJOR ENERGY UTILIZING |
| EQUIPMENT AND ALL BUILDING ENVELOPE COMPONENTS. NO |
| BUILDING ENVELOPE COMPONENTS WERE INCLUDED IN THIS |
| REPORT. IF METHOD A IS TO BE USED, THE WHOLE BUILDING |
| MUST BE DEMONSTRATED TO BE IN COMPLIANCE WITH THE |
| METHOD A CALCULATING PROCEDURES AS DEFINED IN THE |
| FLA/COM PROGRAM. METHOD A MAY ONLY BE USED IF THE |
| CONDITIONS UNDER FBC 13-101.4.2 HAVE BEEN MET. IN |
| ADDITION TO THIS SECTION, PLEASE SEE FBC 13-101.3 TO |
| SEE WHICH COMPLIANCE METHODS ARE AVAILABLE FOR THIS |
| PROJECT. |
| |
| 2. RETURNS HAVE NOT BEEN CHANGED TO SHOW COMPLIANCE |
| WITH THE EXCEPTIONS LISTED UNDER FBC, M 601.4. A FIELD |
| TEST WILL BE REQUIRED AT FINAL INSPECTION DEMONSTRATING |
| PRESSURE DIFFERENTIALS OF 0.01" WC OR LESS IN ROOMS |
| WHERE RETURN JUMPERS ARE UTILIZED. |
| |
| NOTE: PLANS HAVE BEEN REVIEWED FOR CODE COMPLIANCE AND |
| STAMPED. HOWEVER, PLAN REVIEW STOP WILL REMAIN IN |
| "FAILED" STATUS UNTIL A CORRECTED ENERGY CODE |
| COMPLIANCE FORM HAS BEEN SUBMITTED AND REVIEWED. |
| |