Plan Review Notes
Plan Review Notes For Permit 07011175
Permit Number 07011175
Review Stop B
Sequence Number 4
Notes
Date Text
2008-02-08 09:27:56 
  
  
  
  
  
  
 BUILDING PLAN REVIEW
 PERMIT: 07011175
 ADD: 1115 ? 13TH STREET
 CONT: ALL SITE CONST.
 TEL: (561)848-1110
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 4TH
 ACTION: DENIED
 2-7-08
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)OK
  
 4)4TH REQUEST. THE DECLARED VALUE OF THE PROJECT IS
 LOW IN VALUE. IF THE VALUE OF THE PROJECT IS NOT
 INCREASED, THE CITY WILL CALCULATE THE COST OF THE
 PROJECT USING MARSHALL & SWIFT FOR CALCULATION PURPOSES
 LATEST EDITION. 384 SQ FT X 105.10 (ADDITION ALONE) =
 $40,359. THE COST FOR REMODELING THE EXISTING STRUCTURE
 SHALL ALSO BE ADDED TO THE FIGURE MENTION ABOVE. THE
 VALUE SHALL BE THE TOTAL REPLACEMENT COST INCLUDING
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISHES AND
 ARCHITECTURAL DESIGN. WPB AMENDMENTS 108.3
  
 5)4TH REQUEST. A CHANGE IN OCCUPANCY PLUS AN ADDITION
 IMPACT FEES ASSESSMENT: BEFORE A PERMIT TO CONSTRUCT,
 MAY BE ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED
 BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED
 TO THE PERMIT APPLICATION. PLEASE CALL (561) 233-5025
 FOR MORE INFORMATION.
  
 6)4TH REQUEST. PLANS INDICATE THE USE OF 32? DOORS,
 THE 32? POCKET DOORS ARE CODE COMPLIANT BUT THE OTHER
 DOORS THAT ARE 32? WILL NOT PROVIDE A 32? OPENING. FBC
 11-4.13.5 DOORS SHALL HAVE A MINIMUM CLEAR OPENING OF
 32? WITH THE DOOR OPEN 90 DEGREES, MEASURED BETWEEN THE
 FACE OF THE DOOR AND THE OPPOSITE STOP [SEE FIGURE
 24(A,B,C,D)]. PLEASE SEE INFORMATION IN PACKAGE SHOWING
 THE EXAMPLES OF DIFFERENT DOOR TYPES. RESTROOM DOORS
 ARE OK.
  
 NOTE
 7)EXISTING BUILDING CODE, 812.5 ACCESSIBILITY.
 EXISTING BUILDING OR PORTIONS THEREOF THAT UNDER GOES A
 CHANGE IN OCCUPANCY CLASSIFICATION, SHALL COMPLY WITH
 CHAPTER 11 OF THE FLORIDA BUILDING CODE.
  
 NOTE
 8)EXISTING BUILDING CODE 905.1 ACCESSIBILITY
 PROVISIONS FOR NEW ADDITION THAT AFFECTS THE
 ACCESSIBILITY TO OR CONTAIN AN AREA OF, PRIMARY
 FUNCTION SHALL COMPLY WITH THE REQUIREMENTS IN CHAPTER
 11 OF THE FLORIDA BUILDING CODE.
  
 9)4TH REQUEST. PLEASE PROVIDE SITE PLAN INDICATING
 THE HANDICAPPED PARKING AND ACCESSIBLE ROUTE TO THE
 ENTRY 11-4.1.1 (A) (B) 11-4.1.2 (5) (A).
  
 10) 3RD REQUEST. FL BUILDING CODE 1609.1.4 COMPONENTS
 AND CLADDING PROVIDE 2 COPIES OF UPDATED PRODUCT
 APPROVALS FOR THE WINDOWS. THE ONES SUBMITTED WERE
 UNDER THE 2001 CODE VERSION. THERE IS A NEW PRODUCT
 APPROVAL FOR EXTERIOR DOORS IN THE PACKAGE WHICH WAS
 NOT APPROVED BY THE DESIGNER OF RECORD. PLEASE CIRCLE
 OR HI-LIGHT WHICH DOOR WILL BE USED FROM THE PACKAGE.
 THE PRODUCT APPROVAL SHALL BE APPROVED BY THE DESIGNER
 OF RECORD.
  
 11)OK
 12)OK
 13)OK
 14)OK
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 FAX (561) 805-6676
 [email protected]