2008-02-08 09:27:56 | |
| |
| |
| |
| |
| |
| |
| BUILDING PLAN REVIEW |
| PERMIT: 07011175 |
| ADD: 1115 ? 13TH STREET |
| CONT: ALL SITE CONST. |
| TEL: (561)848-1110 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW: 4TH |
| ACTION: DENIED |
| 2-7-08 |
| |
| 1A)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| |
| 3)OK |
| |
| 4)4TH REQUEST. THE DECLARED VALUE OF THE PROJECT IS |
| LOW IN VALUE. IF THE VALUE OF THE PROJECT IS NOT |
| INCREASED, THE CITY WILL CALCULATE THE COST OF THE |
| PROJECT USING MARSHALL & SWIFT FOR CALCULATION PURPOSES |
| LATEST EDITION. 384 SQ FT X 105.10 (ADDITION ALONE) = |
| $40,359. THE COST FOR REMODELING THE EXISTING STRUCTURE |
| SHALL ALSO BE ADDED TO THE FIGURE MENTION ABOVE. THE |
| VALUE SHALL BE THE TOTAL REPLACEMENT COST INCLUDING |
| ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISHES AND |
| ARCHITECTURAL DESIGN. WPB AMENDMENTS 108.3 |
| |
| 5)4TH REQUEST. A CHANGE IN OCCUPANCY PLUS AN ADDITION |
| IMPACT FEES ASSESSMENT: BEFORE A PERMIT TO CONSTRUCT, |
| MAY BE ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH |
| COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED |
| BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED |
| TO THE PERMIT APPLICATION. PLEASE CALL (561) 233-5025 |
| FOR MORE INFORMATION. |
| |
| 6)4TH REQUEST. PLANS INDICATE THE USE OF 32? DOORS, |
| THE 32? POCKET DOORS ARE CODE COMPLIANT BUT THE OTHER |
| DOORS THAT ARE 32? WILL NOT PROVIDE A 32? OPENING. FBC |
| 11-4.13.5 DOORS SHALL HAVE A MINIMUM CLEAR OPENING OF |
| 32? WITH THE DOOR OPEN 90 DEGREES, MEASURED BETWEEN THE |
| FACE OF THE DOOR AND THE OPPOSITE STOP [SEE FIGURE |
| 24(A,B,C,D)]. PLEASE SEE INFORMATION IN PACKAGE SHOWING |
| THE EXAMPLES OF DIFFERENT DOOR TYPES. RESTROOM DOORS |
| ARE OK. |
| |
| NOTE |
| 7)EXISTING BUILDING CODE, 812.5 ACCESSIBILITY. |
| EXISTING BUILDING OR PORTIONS THEREOF THAT UNDER GOES A |
| CHANGE IN OCCUPANCY CLASSIFICATION, SHALL COMPLY WITH |
| CHAPTER 11 OF THE FLORIDA BUILDING CODE. |
| |
| NOTE |
| 8)EXISTING BUILDING CODE 905.1 ACCESSIBILITY |
| PROVISIONS FOR NEW ADDITION THAT AFFECTS THE |
| ACCESSIBILITY TO OR CONTAIN AN AREA OF, PRIMARY |
| FUNCTION SHALL COMPLY WITH THE REQUIREMENTS IN CHAPTER |
| 11 OF THE FLORIDA BUILDING CODE. |
| |
| 9)4TH REQUEST. PLEASE PROVIDE SITE PLAN INDICATING |
| THE HANDICAPPED PARKING AND ACCESSIBLE ROUTE TO THE |
| ENTRY 11-4.1.1 (A) (B) 11-4.1.2 (5) (A). |
| |
| 10) 3RD REQUEST. FL BUILDING CODE 1609.1.4 COMPONENTS |
| AND CLADDING PROVIDE 2 COPIES OF UPDATED PRODUCT |
| APPROVALS FOR THE WINDOWS. THE ONES SUBMITTED WERE |
| UNDER THE 2001 CODE VERSION. THERE IS A NEW PRODUCT |
| APPROVAL FOR EXTERIOR DOORS IN THE PACKAGE WHICH WAS |
| NOT APPROVED BY THE DESIGNER OF RECORD. PLEASE CIRCLE |
| OR HI-LIGHT WHICH DOOR WILL BE USED FROM THE PACKAGE. |
| THE PRODUCT APPROVAL SHALL BE APPROVED BY THE DESIGNER |
| OF RECORD. |
| |
| 11)OK |
| 12)OK |
| 13)OK |
| 14)OK |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |
| (561)805-6726 |
| FAX (561) 805-6676 |
| [email protected] |