2007-11-11 12:49:33 | REVIEW #: 3 |
| ACTION: DENIED |
| |
| FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC |
| CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| |
| THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN |
| RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| *NOTE* A WRITTEN RESPONSE TO REVIEW COMMENTS FROM THE |
| DESIGN TEAM WILL AID IN THE REVIEW PROCESS. |
| |
| 1. ENERGY CALCULATIONS FORM 600 HAS BEEN SUBMITTED FOR |
| THE 3RD TIME. THIS IS NOT A RESIDENTIAL OCCUPANCY, |
| THERE IS A CHANGE OF OCCUPANCY AND SHALL THEREFORE THIS |
| PROJECT SHALL DEMONSTRATE COMPLIANCE WITH FBC |
| 13-101.3. |
| |
| 2. RETURN AIR TRANSFER DUCTS ARE STILL NOT DESIGNED TO |
| MEET TH BALANCED RETURN EXCEPTIONS UNDER FBC,M 601.4. A |
| FIELD TEST WILL BE REQUIRED AT FINAL INSPECTION TO |
| DETERMINE IF PRESSURE DIFFERENTIALS ACROSS CLOSED DOORS |
| ARE AT 0.01IN. WC OR LESS IN ACCORDANCE WITH THIS |
| SECTION. THIS STEP WILL NOT BE NECESSARY IF TRANSFERS |
| ARE DESIGNED TO MEET THE FOLLOWING EXCEPTION: "TRANSFER |
| DUCTS MAY ACHIEVE THIS BY INCREASING THE RETURN |
| TRANSFER ONE AND ONE-HALF TIMES THE CROSS-SECTIONAL |
| AREA (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE |
| ROOM OR SPACE IT IS SERVING AND THE DOOR HAVING AT |
| LEAST AN UNRESTRICTED 1-INCH UNDERCUT TO ACHIEVE PROPER |
| RETURN AIR BALANCE." |
| |
| 3. NATURAL VENTILATION AS SHOWN ON PLANS IS OK. |
| |
| 4. OK |
| |
| 5. OK |
| |
| 6. OK |
| |