2007-10-10 12:37:52*****DENIED*****
 *THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN
 REVIEW STILL NEED TO BE ADDRESSED:
  
 07.SHOW/DISPLAY THE NUMERICAL ADDRESS ON THE
 APPROPIATE EXTERIOR ELEVATION WHICH FRONTS 13TH STREET.
 AS PER WEST PALM BEACH CODE, THOSE NUMBERS SHALL BE NO
 LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN WIDTH
 CONTRASTING TO THE BACKGROUND.(NUMBERS SHALL NOT BE
 ON THE DOOR)PLEASE SHOW ACTUAL ADDRESS NUMBER ON THE
 APPROPIATE EXTERIOR ELEVATION
  
 12.DAY-CARE OCCUPANCIES, OTHER THAN DAY-CARE
 OCCUPANCIES HOUSED IN ONE ROOM, SHALL BE PROVIDED WITH
 A FIRE ALARM SYSTEM (2003 NFPA 101 16.3.4.1).NO FIRE
 ALARM SYSTEM NOTICED IN PLAN;PLEASE EXPLAIN RATIONALE
 FOR A FIRE ALARM SYSTEM NOT REQUIRED
  
  
 *NEW COMMENT
  
 AA.PLEASE EXPLAIN INCLUSION OF FLAMINGO PARK AS PART
 OF THE ADDRESS AS SHOWN IN THE TITLE BLOCK OF THE
 SUBMITTED PL;AN SHEETS.BETTER YET DELETE FLAMINGO
 PARK FROM THE ADDRESS
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 SHEET INDICATING HOW / WHERE ON THE PLANS EACH COMMENT
 WAS ADDRESSED.
  
  