Plan Review Notes
Plan Review Notes For Permit 07011175
Permit Number 07011175
Review Stop E
Sequence Number 3
Notes
Date Text
2007-10-22 18:33:512007-10-22 18:33:51
  
 *** DENIED 3RD REVIEW ***
  
 1) NOTE: ** THIS IS THE FIRST REVIEW UNDER A NEW DESIGN
 TEAM AND ALL NEW PLANS WERE SUBMITTED.
  
 ** PLEASE SEE HOWEVER THERE ARE SEVERAL COMMENTS FROM
 THE TWO PREVIOUS REVIEWS WHICH ARE THE SAME AND STILL
 APPLY. THERE ARE MANY OF THESE WHICH HAVE NOT BEEN
 ADDRESSED AND THERE ARE SOME NEW COMMENTS ONCE AGAIN
 DUE TO THE FACT THAT THERE ARE COMPLETELY NEW PLANS
 SUBMITTED.
  
 ** PLEASE KNOW AS THERE IS STILL INFORMATION NOT
 SUBMITTED OR DESIGNED INTO THE PLANS FOR *MINIMUM* CODE
 COMPLIANCE, AND A FULL AND COMPLETE REVIEW CAN NOT BE
 DONE. THE REVIEW COMMENTS CAN ONLY BE BASED ON PLANS
 AND DOCUMENTS SUBMITTED.
  
 2) NOTE: PLEASE LIST THE BELOW CODES ON ELECTRICAL
 PLANS AS THEY ARE BEING PRINTED BELOW. THE PLANS APPEAR
 TO TAKE PART OF MY PREVIOUS REVIEW COMMENTS AND PLACE
 THIS ON THE SHEETS. PLEASE SEE CODE WHICH SEEMS TO BE
 MISPRINT FOR NEPA. PLEASE ONLY INDICATE THE FOLLOWING.
 2004 FBC W/2006 REVISIONS.
 2005 NPPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** SOME ARE OK, HOWEVER NOT ALL AND ONLY MINOR
 ADJUSTMENTS ARE NEEDED. PLANS ARE COMING BACK FOR
 CORRECTIONS AT THIS TIME.
  
 3) NOTE: PLEASE COMPLETE AND CORRELATE ALL CIRCUITING
 ON PLANS. PLEASE SEE THAT THERE ARE CIRCUITS ON PLANS
 FOR EXAMPLE FOR 120V GFI LOADS WHICH ARE SHOWN
 CIRCUITED TO A/C SYSTEM WHICH IS NOT POSSIBLE. PLEASE
 SEE FOR EXAMPLE: CIRCUITS 18 AND 19 ON PLANS. PLEASE
 SEE 700.12F FOR CIRCUITING OF EMERGENCY AND EXIT
 LIGHTS. THESE ARE REQUIRED TO BE CIRCUITED TO THE
 NORMAL LIGHTING BRANCH CIRCUITS IN THE AREAS IN WHICH
 THEY ARE LOCATED.
 FBC 106.1.2, 106.3.5.1.2, 106.3.1. ETC
 NEC 408.4, 310.16, 240.4.
 PLEASE SEE THE FOLLOWING STATEMENT WHICH IS TAKEN
 DIRECTLY FROM THE NEC.
 *2005 CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY
 CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE
 LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR
 WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME
 PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR
 EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY
 OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN
 COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL
 APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD,
 THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL
 RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR
 ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.''
 CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH
 ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE
 SUFFICIENT DETAIL REQUIRED BY THIS SECTION*
 **SAME COMMENT ON TWO PREVIOUS REVIEWS.
  
 4) NOTE: PLEASE LABEL ALL LIGHTING FIXTURES ON PLANS
 AND CORRELATE WITH A COMPLETE FIXTURE LEGEND FOR
 FIXTURES WHICH INDICATE TYPE AND ANY SAFETY ASPECTS FOR
 FIXTURES (ENCLOSED LENSES ETC REQUIRED) PLEASE BE SURE
 FIXTURES SPECIFIED MEET THE LIFE SAFETY CODE FOR DAY
 CARE OCCUPANCIES.
 A COMPLETED FIXTURE LEGEND OF FIXTURES IS REQUIRED. FBC
 106.1.2 LS 101 CHAPTER 16.
 **SAME COMMENT ON PREVIOUS TWO REVIEWS.
  
 5) NOTE:THIS WAS THE SAME COMMENT FROM TWO PREVIOUS
 REVIEWS AND YET NO COMPLIANCE WITH FBC CHAPTER 13 OR
 CALCULATIONS HAS BEEN SUBMITTED.
 PLEASE SUBMIT COMPLETE ENERGY CALCULATIONS TO MEET THE
 2004 FBC 13-415.1.AB.1.
 PLEASE ALSO PROVIDE INFORMATION ON LIGHTING POWER
 DENSITIES PER 13-415.2
 PLEASE SEE THAT NONE WERE SUBMITTED.
 PLEASE ALSO SEE 13-103.1.1.1 FOR REQUIRED
 CERTIFICATIONS.
 ** SAME AS TWO PREVIOUS REVIEWS.
  
 6) NOTE: PLEASE SEE LS-101 16.5.1.2
 SPECIAL PROTECTIVE COVERS FOR ALL ELECTRICAL
 RECEPTACLES SHALL BE INSTALLED IN ALL AREAS OCCUPIED BY
 CLIENTS.
 PLEASE KNOW THAT THIS DOES NOT MEAN THE PLASTIC PLUG-IN
 TYPE DEVICES, THIS MEANS THE RECEPTACLE DEVICE SHALL BE
 LISTED FOR USE (110.3) AND BE OF THE TYPE WHICH
 PROVIDES AUTOMATIC PROTECTION IF AN APPLIANCE IS NOT
 PLUGGED IN OR IN USE.
 ** SAME AS TWO PREVIOUS REVIEWS. MAY NOT QUOTE THE CODE
 OR REQUIREMENT IN LIEU OF ACTUAL DESIGN OR SPECIFIC
 DETAILS NEEDED. 106.1.2
  
 7) NOTE: PLEASE SEE LS 101 2003, 6.1.4.1 FOR USE,
 9.6.4, 16.3.4.5.
 PLEASE SEE ALL SMOKE DETECTION DEVICES AND SYSTEM SHALL
 BE SHOWN.
 THIS IS NOT A RESIDENCE OR SINGLE FAMILY DWELLING.
 PLEASE SEE REVIEW COMMENTS FROM FIRE MARSHAL AS FIRE
 ALARM SYSTEM IS REQUIRED.
 PLEASE SEE FBC 11-4.28.1,.2 AND .3(4) FOR MINIMUM
 LOCATIONS AND DEVICE LEVELS TO MEET ADA.
  
  
 8) NOTE: PLEASE INDICATE THE MINIMUM LEVELS FOR EGRESS
 LIGHTING PER 7.8., 7.9.
 PLEASE SEE 106.1.2 FBC FOR ADDITIONAL INFORMATION
 NEEDED.
  
 9) NOTE: THE LOAD CALCULATIONS SUBMITTED ONCE AGAIN ARE
 FOR A RESIDENTIAL USE AND NOT FOR COMMERCIAL. PLEASE
 REVISE AND CORRECT.
 PLEASE SEE THE LOAD CALCULATIONS SHALL MEET 2005 NEC,
 THESE ARE SUBMITTED AND SHOWN FOR DWELLING USE AND
 OCCUPANCY.
 PLEASE SEE 220.3, 220.12, 220.14, 220.42, 220.44,
 PLEASE BE SURE ALL CONTINUOUS LOADS AT SHOWN AT 125%.
 215.3, 230.42
 ** SAME NOTE AS TWO PREVIOUS REVIEWS.
  
 10) NOTE: PLEASE SEE THE NOTE #3 ON PANEL SCHEDULE
 NOTES MENTIONS * AHU IS NOW- CONCURRENT WITH CONDENSING
 UNIT*.
 PLEASE VERIFY THIS AS THIS IS MOST LIKELY NOT WHAT IS
 MEANT TO BE NOTED. PLEASE SEE 220.60 WHICH IS FOR A/C.
 THIS IS EXTRACTED FROM THE NEC BELOW FOR CLARIFICATION
 OF CODE.
 *220.60 NONCOINCIDENT LOADS
 WHERE IT IS UNLIKELY THAT TWO OR MORE NONCOINCIDENT
 LOADS WILL BE IN USE SIMULTANEOUSLY, IT SHALL BE
 PERMISSIBLE TO USE ONLY THE LARGEST LOAD(S) THAT WILL
 BE USED AT ONE TIME FOR CALCULATING THE TOTAL LOAD OF A
 FEEDER OR SERVICE.*
  
 11) NOTE: PLEASE SEE MISSING DISCONNECT FOR WATER
 HEATER. PLANS SHOW A RECEPTACLE WHICH CAN NOT BE USED
 FOR CONNECTION OF WATER HEATERS. 422.30, 422.31.
  
 12) NOTE: PLEASE SEE 422.13 AS STORAGE TYPE WATER
 HEATERS ARE NOW CONSIDERED UNDER THE 2005 NEC AS A
 CONTINUOUS LOADS WHICH REQUIRES LOAD TO BE FIGURED AT
 125% IN CALCULATIONS.
 PLEASE SEE NOTE # 9 ABOVE AS ALL CALCULATIONS WILL BE
 ADJUSTED.
  
 13) NOTE: PLEASE PROVIDE ALL LICENSE INFORMATION AS
 REQUIRED FOR ALL DESIGNERS ON PLANS AS LICENSED UNDER
 FS 481.
 PLEASE SEE 481.229 AS *DESIGNERS/DRAFTSPERSONS* NOT
 LICENSED UNDER FS 481 MAY NOT DESIGN OR DO COMMERCIAL
 WORK AS IN THE SCOPE AS LISTED ON PLANS.
 PLEASE ADJUST TITLE BLOCKS WHICH REMOVES THE DESIGNER
 AS SHOWN ON INCLUDE THE LICENSE INFORMATION AS REQUIRED
 PER FAC61G1-16.004, FS 481.
 ** THE COMMENT IS NOT FOR MR. WRONKSKY.
 ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY ANY OF THE OTHER
 TRADE REVIEWS.
  
 14) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCTOR FROM MAIN TO SUB PANEL.
 250.110, 250.24, 250.122 ETC.
  
 15) NOTE: PLEASE KNOW WITH RESPECT TO FS 553.80(2)(B),
 THE FEE AS REQUIRED BY THE FLORIDA STATUES AS NOTED
 WHICH WOULD HAVE BEEN ASSESSED IS NOT ASSESSED DUE TO
 NEW DESIGN TEAM.
  
 ** PLEASE KNOW AS MENTIONED ABOVE, AS THERE WILL BE
 SEVERAL CHANGES ON PLANS AND AS THERE ARE SEVERAL ITEMS
 NOT SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW
 COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE
 AT THIS TIME.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]