2007-10-22 18:33:51 | 2007-10-22 18:33:51 |
| |
| *** DENIED 3RD REVIEW *** |
| |
| 1) NOTE: ** THIS IS THE FIRST REVIEW UNDER A NEW DESIGN |
| TEAM AND ALL NEW PLANS WERE SUBMITTED. |
| |
| ** PLEASE SEE HOWEVER THERE ARE SEVERAL COMMENTS FROM |
| THE TWO PREVIOUS REVIEWS WHICH ARE THE SAME AND STILL |
| APPLY. THERE ARE MANY OF THESE WHICH HAVE NOT BEEN |
| ADDRESSED AND THERE ARE SOME NEW COMMENTS ONCE AGAIN |
| DUE TO THE FACT THAT THERE ARE COMPLETELY NEW PLANS |
| SUBMITTED. |
| |
| ** PLEASE KNOW AS THERE IS STILL INFORMATION NOT |
| SUBMITTED OR DESIGNED INTO THE PLANS FOR *MINIMUM* CODE |
| COMPLIANCE, AND A FULL AND COMPLETE REVIEW CAN NOT BE |
| DONE. THE REVIEW COMMENTS CAN ONLY BE BASED ON PLANS |
| AND DOCUMENTS SUBMITTED. |
| |
| 2) NOTE: PLEASE LIST THE BELOW CODES ON ELECTRICAL |
| PLANS AS THEY ARE BEING PRINTED BELOW. THE PLANS APPEAR |
| TO TAKE PART OF MY PREVIOUS REVIEW COMMENTS AND PLACE |
| THIS ON THE SHEETS. PLEASE SEE CODE WHICH SEEMS TO BE |
| MISPRINT FOR NEPA. PLEASE ONLY INDICATE THE FOLLOWING. |
| 2004 FBC W/2006 REVISIONS. |
| 2005 NPPA-70 |
| 2002 NFPA-72 |
| 2003 NFPA-101 |
| |
| ** SOME ARE OK, HOWEVER NOT ALL AND ONLY MINOR |
| ADJUSTMENTS ARE NEEDED. PLANS ARE COMING BACK FOR |
| CORRECTIONS AT THIS TIME. |
| |
| 3) NOTE: PLEASE COMPLETE AND CORRELATE ALL CIRCUITING |
| ON PLANS. PLEASE SEE THAT THERE ARE CIRCUITS ON PLANS |
| FOR EXAMPLE FOR 120V GFI LOADS WHICH ARE SHOWN |
| CIRCUITED TO A/C SYSTEM WHICH IS NOT POSSIBLE. PLEASE |
| SEE FOR EXAMPLE: CIRCUITS 18 AND 19 ON PLANS. PLEASE |
| SEE 700.12F FOR CIRCUITING OF EMERGENCY AND EXIT |
| LIGHTS. THESE ARE REQUIRED TO BE CIRCUITED TO THE |
| NORMAL LIGHTING BRANCH CIRCUITS IN THE AREAS IN WHICH |
| THEY ARE LOCATED. |
| FBC 106.1.2, 106.3.5.1.2, 106.3.1. ETC |
| NEC 408.4, 310.16, 240.4. |
| PLEASE SEE THE FOLLOWING STATEMENT WHICH IS TAKEN |
| DIRECTLY FROM THE NEC. |
| *2005 CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY |
| CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE |
| LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR |
| WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME |
| PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR |
| EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY |
| OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN |
| COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL |
| APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD, |
| THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL |
| RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR |
| ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.'' |
| CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH |
| ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE |
| SUFFICIENT DETAIL REQUIRED BY THIS SECTION* |
| **SAME COMMENT ON TWO PREVIOUS REVIEWS. |
| |
| 4) NOTE: PLEASE LABEL ALL LIGHTING FIXTURES ON PLANS |
| AND CORRELATE WITH A COMPLETE FIXTURE LEGEND FOR |
| FIXTURES WHICH INDICATE TYPE AND ANY SAFETY ASPECTS FOR |
| FIXTURES (ENCLOSED LENSES ETC REQUIRED) PLEASE BE SURE |
| FIXTURES SPECIFIED MEET THE LIFE SAFETY CODE FOR DAY |
| CARE OCCUPANCIES. |
| A COMPLETED FIXTURE LEGEND OF FIXTURES IS REQUIRED. FBC |
| 106.1.2 LS 101 CHAPTER 16. |
| **SAME COMMENT ON PREVIOUS TWO REVIEWS. |
| |
| 5) NOTE:THIS WAS THE SAME COMMENT FROM TWO PREVIOUS |
| REVIEWS AND YET NO COMPLIANCE WITH FBC CHAPTER 13 OR |
| CALCULATIONS HAS BEEN SUBMITTED. |
| PLEASE SUBMIT COMPLETE ENERGY CALCULATIONS TO MEET THE |
| 2004 FBC 13-415.1.AB.1. |
| PLEASE ALSO PROVIDE INFORMATION ON LIGHTING POWER |
| DENSITIES PER 13-415.2 |
| PLEASE SEE THAT NONE WERE SUBMITTED. |
| PLEASE ALSO SEE 13-103.1.1.1 FOR REQUIRED |
| CERTIFICATIONS. |
| ** SAME AS TWO PREVIOUS REVIEWS. |
| |
| 6) NOTE: PLEASE SEE LS-101 16.5.1.2 |
| SPECIAL PROTECTIVE COVERS FOR ALL ELECTRICAL |
| RECEPTACLES SHALL BE INSTALLED IN ALL AREAS OCCUPIED BY |
| CLIENTS. |
| PLEASE KNOW THAT THIS DOES NOT MEAN THE PLASTIC PLUG-IN |
| TYPE DEVICES, THIS MEANS THE RECEPTACLE DEVICE SHALL BE |
| LISTED FOR USE (110.3) AND BE OF THE TYPE WHICH |
| PROVIDES AUTOMATIC PROTECTION IF AN APPLIANCE IS NOT |
| PLUGGED IN OR IN USE. |
| ** SAME AS TWO PREVIOUS REVIEWS. MAY NOT QUOTE THE CODE |
| OR REQUIREMENT IN LIEU OF ACTUAL DESIGN OR SPECIFIC |
| DETAILS NEEDED. 106.1.2 |
| |
| 7) NOTE: PLEASE SEE LS 101 2003, 6.1.4.1 FOR USE, |
| 9.6.4, 16.3.4.5. |
| PLEASE SEE ALL SMOKE DETECTION DEVICES AND SYSTEM SHALL |
| BE SHOWN. |
| THIS IS NOT A RESIDENCE OR SINGLE FAMILY DWELLING. |
| PLEASE SEE REVIEW COMMENTS FROM FIRE MARSHAL AS FIRE |
| ALARM SYSTEM IS REQUIRED. |
| PLEASE SEE FBC 11-4.28.1,.2 AND .3(4) FOR MINIMUM |
| LOCATIONS AND DEVICE LEVELS TO MEET ADA. |
| |
| |
| 8) NOTE: PLEASE INDICATE THE MINIMUM LEVELS FOR EGRESS |
| LIGHTING PER 7.8., 7.9. |
| PLEASE SEE 106.1.2 FBC FOR ADDITIONAL INFORMATION |
| NEEDED. |
| |
| 9) NOTE: THE LOAD CALCULATIONS SUBMITTED ONCE AGAIN ARE |
| FOR A RESIDENTIAL USE AND NOT FOR COMMERCIAL. PLEASE |
| REVISE AND CORRECT. |
| PLEASE SEE THE LOAD CALCULATIONS SHALL MEET 2005 NEC, |
| THESE ARE SUBMITTED AND SHOWN FOR DWELLING USE AND |
| OCCUPANCY. |
| PLEASE SEE 220.3, 220.12, 220.14, 220.42, 220.44, |
| PLEASE BE SURE ALL CONTINUOUS LOADS AT SHOWN AT 125%. |
| 215.3, 230.42 |
| ** SAME NOTE AS TWO PREVIOUS REVIEWS. |
| |
| 10) NOTE: PLEASE SEE THE NOTE #3 ON PANEL SCHEDULE |
| NOTES MENTIONS * AHU IS NOW- CONCURRENT WITH CONDENSING |
| UNIT*. |
| PLEASE VERIFY THIS AS THIS IS MOST LIKELY NOT WHAT IS |
| MEANT TO BE NOTED. PLEASE SEE 220.60 WHICH IS FOR A/C. |
| THIS IS EXTRACTED FROM THE NEC BELOW FOR CLARIFICATION |
| OF CODE. |
| *220.60 NONCOINCIDENT LOADS |
| WHERE IT IS UNLIKELY THAT TWO OR MORE NONCOINCIDENT |
| LOADS WILL BE IN USE SIMULTANEOUSLY, IT SHALL BE |
| PERMISSIBLE TO USE ONLY THE LARGEST LOAD(S) THAT WILL |
| BE USED AT ONE TIME FOR CALCULATING THE TOTAL LOAD OF A |
| FEEDER OR SERVICE.* |
| |
| 11) NOTE: PLEASE SEE MISSING DISCONNECT FOR WATER |
| HEATER. PLANS SHOW A RECEPTACLE WHICH CAN NOT BE USED |
| FOR CONNECTION OF WATER HEATERS. 422.30, 422.31. |
| |
| 12) NOTE: PLEASE SEE 422.13 AS STORAGE TYPE WATER |
| HEATERS ARE NOW CONSIDERED UNDER THE 2005 NEC AS A |
| CONTINUOUS LOADS WHICH REQUIRES LOAD TO BE FIGURED AT |
| 125% IN CALCULATIONS. |
| PLEASE SEE NOTE # 9 ABOVE AS ALL CALCULATIONS WILL BE |
| ADJUSTED. |
| |
| 13) NOTE: PLEASE PROVIDE ALL LICENSE INFORMATION AS |
| REQUIRED FOR ALL DESIGNERS ON PLANS AS LICENSED UNDER |
| FS 481. |
| PLEASE SEE 481.229 AS *DESIGNERS/DRAFTSPERSONS* NOT |
| LICENSED UNDER FS 481 MAY NOT DESIGN OR DO COMMERCIAL |
| WORK AS IN THE SCOPE AS LISTED ON PLANS. |
| PLEASE ADJUST TITLE BLOCKS WHICH REMOVES THE DESIGNER |
| AS SHOWN ON INCLUDE THE LICENSE INFORMATION AS REQUIRED |
| PER FAC61G1-16.004, FS 481. |
| ** THE COMMENT IS NOT FOR MR. WRONKSKY. |
| ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES |
| WHETHER OR NOT COMMENT IS MADE BY ANY OF THE OTHER |
| TRADE REVIEWS. |
| |
| 14) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING |
| CONDUCTOR FROM MAIN TO SUB PANEL. |
| 250.110, 250.24, 250.122 ETC. |
| |
| 15) NOTE: PLEASE KNOW WITH RESPECT TO FS 553.80(2)(B), |
| THE FEE AS REQUIRED BY THE FLORIDA STATUES AS NOTED |
| WHICH WOULD HAVE BEEN ASSESSED IS NOT ASSESSED DUE TO |
| NEW DESIGN TEAM. |
| |
| ** PLEASE KNOW AS MENTIONED ABOVE, AS THERE WILL BE |
| SEVERAL CHANGES ON PLANS AND AS THERE ARE SEVERAL ITEMS |
| NOT SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW |
| COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE |
| AT THIS TIME. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |