Date |
Text |
2007-05-22 14:04:49 | |
| |
| PAUL SCHMITZ |
| |
| [email protected] |
| FBC 2004 PLUMBING CODE |
| PLAN REVIEW |
| FBC 2004 FUEL GAS CODE PLAN REVIEW FBC |
| 2004 CH 11, FL ACCESSIBILITY CODE AMENDMENTS TO THE |
| FLORIDA BUILDING CODE |
| CHAPT.1, ADMINISTRATION, 2004 |
| EDITION |
| |
| DENIED 2ND |
| TIME 5-22-07 |
| "SEE COMMENTS IN CAPITOL |
| LETTERS" |
| |
| NOT ADDRESSED |
| 1)SHT 3. BOYS & GIRLS REST ROOM |
| COMPLY WITH 36 CFR PART 1191 [ DOCKET NO.94-2]"GUIDE |
| LINES" |
| ADA ACCESSIBILITY GUIDELINES FOR BUILDINGS AND |
| FACILITIES; BUILDING ELEMENTS DESIGNED FOR CHILDREN'S |
| USE. |
| |
| SHT 3. LABEL DRINKING FOUNTAIN AS D/F, WHY, 3 W/F |
| ? |
| 2) SHT 3.11-4.1.3 (10)DRINKING FOUNTAINS. |
| (A) WHERE ONLY ONE DRINKING FOUNTAIN IS PROVIDED ON A |
| FLOOR, THERE SHALL BE A DRINKING FOUNTAIN WHICH IS |
| ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS IN |
| ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE TO |
| THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING. (THIS |
| CAN BE ACCOMMODATED BY THE USE OF A ?HI-LO? FOUNTAIN; |
| BY PROVIDING ONE FOUNTAIN ACCESSIBLE TO THOSE WHO USE |
| WHEELCHAIRS AND ONE FOUNTAIN AT A STANDARD HEIGHT |
| CONVENIENT FOR THOSE WHO HAVE DIFFICULTY BENDING; BY |
| PROVIDING A FOUNTAIN ACCESSIBLE UNDER SECTION 11-4.15 |
| AND A WATER COOLER; OR BY SUCH OTHER MEANS AS WOULD |
| ACHIEVE THE REQUIRED ACCESSIBILITY FOR EACH GROUP ON |
| EACH FLOOR.) |
| |
| DIMENSIONS ON BOYS AND GIRLS REST RM, |
| WIDTH NOT TO SCALE, MIN 5'-2" |
| 3) SEC. (11) 11-4.1.3 ACCESSIBLE BUILDINGS: NEW |
| CONSTRUCTION, TOILET FACILITIES. IF TOILET ROOMS ARE |
| PROVIDED, THEN EACH PUBLIC AND COMMON USE TOILET ROOM |
| SHALL COMPLY WITH SECTION 11-4.22. OTHER TOILET ROOMS |
| PROVIDED FOR THE USE OF OCCUPANTS OF SPECIFIC SPACES |
| (I.E., A PRIVATE TOILET ROOM FOR THE OCCUPANT OF A |
| PRIVATE OFFICE) SHALL BE ADAPTABLE. IF BATHING ROOMS |
| ARE PROVIDED, THEN EACH PUBLIC AND COMMON USE BATHROOM |
| SHALL COMPLY WITH SECTION 11-4.23. ACCESSIBLE TOILET |
| ROOMS AND BATHING FACILITIES SHALL BE ON AN ACCESSIBLE |
| ROUTE. |
| |
| WATER PIPING ISOMETRIC NOT INCLUDED |
| 4) SHT 4. COMPLY WITH SEC 106 SANITARY AND WATER PIPE |
| ISOMETRIC, INCLUDE PIPE SIZES ON THE ISOMETRICS. |
| SHT 4 PLUMBING NOTES ARE NOT SUFFICENT TO INDICATE |
| NATURE OF WORK. |
| 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE |
| OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL (SEE ALSO SECTION |
| 106.3.5). |
| |
| |
| NOT ADDRESSED |
| 5)SECTION 608, BACK FLOW PREVENTER |
| PROTECTION OF POTABLE WATER SUPPLY |
| 608.1 GENERAL. |
| A POTABLE WATER SUPPLY SYSTEM SHALL BE DESIGNED, |
| INSTALLED AND MAINTAINED IN SUCH A MANNER SO AS TO |
| PREVENT CONTAMINATION FROM NONPOTABLE LIQUIDS, SOLIDS |
| OR GASES BEING INTRODUCED INTO THE POTABLE WATER SUPPLY |
| THROUGH CROSS-CONNECTIONS OR ANY OTHER PIPING |
| CONNECTIONS TO THE SYSTEM. BACKFLOW PREVENTER |
| APPLICATIONS SHALL CONFORM TO TABLE 608.1, EXCEPT AS |
| SPECIFICALLY STATED IN SECTIONS 608.2 THROUGH |
| 608.16.9. |
| |
| NOT ADDRESSED |
| 6) SEC 607.3 THERMAL EXPANSION CONTROL. |
| A MEANS OF CONTROLLING INCREASED PRESSURE CAUSED BY |
| THERMAL EXPANSION SHALL BE PROVIDED WHERE REQUIRED IN |
| ACCORDANCE WITH SECTIONS 607.3.1 AND 607.3.2. 607.3.2 |
| BACKFLOW PREVENTION DEVICE OR CHECK VALVE. WHERE A |
| BACKFLOW PREVENTION DEVICE, CHECK VALVE OR OTHER DEVICE |
| IS INSTALLED ON A WATER SUPPLY SYSTEM UTILIZING STORAGE |
| WATER HEATING EQUIPMENT SUCH THAT THERMAL EXPANSION |
| CAUSES AN INCREASE IN PRESSURE, A DEVICE FOR |
| CONTROLLING PRESSURE SHALL BE INSTALLED. |
| |
| NOT ADDRESSED |
| 7)SEE OTHER PLAN REVIEW COMMENTS, THAT MAY EFFECT |
| PLUMBING PLAN REVIEW. |
| |
| 8) NEW COMMENT:HEALTH DEPARTMENT NOTES, CHILD CHANGE |
| STATIONS TO BE INCLUDED ON REVISEED PLANS. |
| |
| 9) NEW COMMENT: SERVICE AREA IS NOT EXISTING, INCLUDE |
| ON DWV, WATER ISOMETRIC. |
| |
| END OF COMMENTS, QUESTIONS 561-805-6692 |