2007-05-14 11:40:39 | -------------DENIED--------------- |
| |
| FBC 2004 CODE FAMILY W/2006 REVISIONS |
| |
| 1. FORM 600 OF THE ENERGY CALCULATIONS IS NOT |
| ACCEPTABBLE FOR THIS PROJECT AS THIS IS NO LONGER A |
| RESIDENTIAL OCCUPANCY. PLEASE ALSO INCLUDE COOLING LOAD |
| CALCULATIONS PER FBC CH 13-B SEC. 3.1. IS THIS SYSTEM |
| ADEQUATELY SIZED FOR THE ADDITIONAL SQ' FOOTAGE, |
| INCREASED OCCUPANT LOAD AND 600 CFM OUTSIDE AIR? |
| NOTE: THE MINIMUM EFFICIENCY FOR SPLIT SYSTEMS <65,000 |
| BTUH AS REQUIRED BY TABLE 13-407.1.ABC.3.2A IS 13.0 |
| SEER. |
| |
| 2. THERE IS NO RETURN AIR SHOWN ON PLAN, OTHER THAN THE |
| 12" ROUND TRANSFER FROM INFANT ROOM. WHAT IS THE SIZE |
| AND LOCATION OF MAIN RETURN? HOW IS BALANCED RETURN TO |
| BE ACHIEVED FROM OFFICE AND SERVICE AREA (IF IT IS NOT |
| TO BE A KITCHEN)? |
| NOTE: THE TRANSFER FROM INFANT ROOM DOES NOT MEET THE |
| EXCEPTIONS TO FBC,M 601.4. PLEASE DESIGN ALL TRANSFERS |
| TO THESE EXCEPTIONS OR A FIELD TEST WILL BE REQUIRED AT |
| FINAL INSPECTION TO DETERMINE PRESSURE DIFFERENTIALS AS |
| REQUIRED BY THIS SECTION. |
| |
| 3. VENTILATION SHALL BE PROVIDED TO ALL OCCUPUED SPACES |
| (IE: KITCHEN/SERVICE AREA AND OFFICE) PER FBC,M 403.1. |
| THE AMOUNT OF SUPPLY AIR IS TO BE APPROXIMATELY EQUAL |
| TO THE AMOUNT OF RETURN AND EXHAUST AIR PER FBC,M |
| 403.1. RETURN SHOULD BE 600 CFM LESS THAN SUPPLY WITH |
| 600 CFM OF EXHAUST. WHERE IS EXHAUST? |
| |
| 4. EXHAUST AIR IS REQUIRED FOR BATHROOMS PER FBC,M |
| TABLE 403.3 UNDER PUBLIC SPACES - TOILET ROOMS. |
| |
| 5. THE VENTILATION SYSTE SHALL RUN CONTINUOUSLY DURING |
| THE PERIOD THE BUILDING IS OCCUPIED PER FBC,M 403.3. |
| PLEASE SHOW HOW THE SYSTEM IS TO BE CONTROLLED TO |
| ACCOMPLISH THIS? |
| |
| 6. WHAT TYPE OF COOKING EQUIPMENT IS THE BE IN THE |
| SERVICE AREA? KITCHEN EXHAUST IS TO BE IN COMPLIANCE |
| WITH FBC,M CH. 506 PER FBC,EB 809.1. |
| |