2007-05-22 17:04:42 | *****DENIED***** |
| THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN |
| REVIEW STILL NEED TO BE ADDRESSED: |
| |
| |
| 01.THE LIFE SAFETY CODE, NFPA 101, 2003 EDITION SHALL |
| BE REFERENCED. |
| |
| 02.PROVIDE THE OCCUPANT LOAD, IN NUMBER OF PERSONS |
| FOR WHOM MEANS OF EGRESS AND OTHER PROVISIONS ARE |
| REQUIRED,EITHER SHALL BE DETERMINED ON THE BASIS OF |
| THE OCCUPANT LOAD FACTORS OF TABLE 7.3.1.2 THAT ARE |
| CHARACTERISTIC OF THE USE OF THE SPACE OR SHALL BE |
| DETERMINED AS THE MAXIMUMPROBABLE POPULATION OF THE |
| SPACE UNDER CONSIDERATION, WHICHEVER IS GREATER. |
| |
| 03.IF THE OCCUPANT LOAD IS DETERMINED BASED UPON THE |
| MAXIMUM PROBABLE POPULATION OF THE SPACE, AN APPROVED |
| AISLE, SEATING, AND EXITING DIAGRAM SHALL BE REQUIRED |
| TO SUBSTANTIATE SUCH A MODIFICATION. |
| |
| 04.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| |
| 05.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS |
| SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT |
| OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. |
| |
| 06.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF |
| NEW BUILDING MATERIALS & SUPPLIES SHALL NOT INTERFERE |
| OR HINDER WITH EMERGENCY RESPONSE ACCESS TO THE SAID |
| PROPERTY OR VICINITY THEREOF (INCLUDING STREETS OR |
| ROADWAYS). |
| |
| 07.SHOW/DISPLAY THE NUMERICAL ADDRESS ON THE |
| APPROPIATE EXTERIOR ELEVATION WHICH FRONTS 13TH STREET. |
| AS PER WEST PALM BEACH CODE, THOSE NUMBERS SHALL BE NO |
| LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN WIDTH |
| CONTRASTING TO THE BACKGROUND.(NUMBERS SHALL NOT BE |
| ON THE DOOR) |
| |
| 08.PROVIDE A LIFE SAFETY PLAN SHEET WHICH INDICATES |
| THE TRAVEL DISTANCE TO THE EXITS.THIS SHEET MAY ALSO |
| INCLUDE THE LOCATION OF THE EXIT LIGHTS, EMERGENCY |
| LIGHTS, FIRE ALARM DEVICES, AND THE 2A:10BC RATED FIRE |
| EXTINGUISHERS APPLICABLE TO THE PROPOSED STRUCTURE. |
| |
| 09.EVERY CLOSET DOOR LATCH SHALL BE SUCH THAT CLIENTS |
| CAN OPEN THE DOOR FROM INSIDE THE CLOSET. |
| |
| 10.EVERY BATHROOM DOOR LOCK SHALL BE DESIGNED TO |
| ALLOW OPENING OF THE LOCKED DOOR FROM THE OUTSIDE BY AN |
| OPENING DEVICE THAT SHALL BE READILY ACCESSSIBLE TO THE |
| STAFF. |
| |
| 11.INTERIOR WALL AND CEILING FINISH MATERIALS SHALL |
| BE CLASS A OR CLASS B. |
| |
| 12.DAY-CARE OCCUPANCIES, OTHER THAN DAY-CARE |
| OCCUPANCIES HOUSED IN ONE ROOM, SHALL BE PROVIDED WITH |
| A FIRE ALARM SYSTEM. |
| |
| 13.OTHER THAN THOSE HOUSED IN ONE ROOM, A SMOKE |
| DETECTION SYSTEM SHALL BE INSTALLED IN DAY-CARE |
| OCCUPANCIES. |
| |
| 14.SPECIAL PROTECTIVE COVERINGS FOR ALL ELECTRICAL |
| RECEPTACLES SHALL BE INSTALLED IN ALL AREAS OCCUPIED BY |
| THE CLIENTS. |
| |
| 15.ADEQUATE ADULT STAFF SHALL BE ON DUTY, ALERT, |
| AWAKE, AND IN THE FACILITY AT ALL TIMES WHERE CLIENTS |
| ARE PRESENT. |
| |
| |
| TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| SHEET INDICATING HOW / WHERE ON THE PLANS EACH COMMENT |
| WAS ADDRESSED. |
| |
| |