Plan Review Notes
Plan Review Notes For Permit 07011175
Permit Number 07011175
Review Stop E
Sequence Number 2
Notes
Date Text
2007-05-11 09:16:18** UNSAT2ND REVIEW **
  
 ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA
 BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED
 BY THE CITY OF WEST PALM BEACH.
  
 *** PLEASE SEE THAT IS A CHANGE IN OCCUPANCY TO DAY
 CARE FACILITY.
  
 1) NOTE: PLEASE STATE AND DESIGN TO ALL OF THE
 FOLLOWING MINIMUM CODES AT A MINIMUM FOR ELECTRICAL
 REVIEW.
 NFPA-70 2005 (2002 STATES ON PLANS), 2002 NFPA-72, 2003
 NFPA-101, 2004 FBCW/2006 REVISIONS.
 PLEASE SEE MISPRINT ON ELECTRICAL SHEETS ALONG WITH THE
 CODE AND ?BUILDING LEVEL? ? BEING SHOWN AS #2?
 ** PLEASE SEE THAT THE PLANS STATE A *LEVEL 2
 ALTERATION*, HOW IS THIS POSSIBLE WHEN THIS IS A CHANGE
 IN OCCUPANCY AND ALL SHALL BE DESIGNED TO THE NEW AND
 CURRENT CODES.
  
 2) NOTE: PLEASE BE SURE PLANS ARE DONE IN A CLEAR AND
 PRINTED MANOR WHICH ARE A MINIMUM OF DRAFTSMAN QUALITY
 AS REQUIRED UNDER FBC 106.1.3
  
 3) NOTE:SAME COMMENT, NO INFORMATION SUBMITTED.
 PLEASE LABEL ALL LIGHTING FIXTURES ON PLANS AND
 CORRELATE WITH A COMPLETE FIXTURE LEGEND FOR FIXTURES
 WHICH INDICATE TYPE AND ANY SAFETY ASPECTS FOR FIXTURES
 (ENCLOSED LENSES ETC REQUIRED) PLEASE BE SURE FIXTURES
 SPECIFIED MEET THE LIFE SAFETY CODE FOR DAY CARE
 OCCUPANCIES.
 PLEASE ALSO SEE THESE LIGHTING FIXTURES AND SCHEDULES
 MUST MEET THE FLA-COM CALCULATIONS FOR CHAPTER 13 OF
 THE FBC 2004 W/2006 REVISONS.
 FBC 106.1.2 LS 101 CHAPTER 16.
  
 4) NOTE: SAME NOTE: PLEASE SUBMIT COMPLETE ENERGY
 CALCULATIONS TO MEET THE 2004 FBC 13-415.1.AB.1.ETC
 PLEASE BE SURE COORDINATE ALL FIXTURES ON PLANS WITH
 THAT OF THE FIXTURE SCHEDULE AND CALCULATIONS. PLEASE
 ALSO PROVIDE INFORMATION ON LIGHTING POWER DENSITIES
 PER 13-415.2
 PLEASE SEE THE ENERGY CALCULATIONS NOW SUBMITTED ARE
 METHOD B FOR RESIDENTIAL. THIS IS NOT A RESIDENTIAL
 OCCUPANCY AND MAY NOT USE THIS. PLEASE ALSO SEE THAT
 WHEN THE CORRECTED CALCULATIONS ARE SUBMITTED, THESE
 ARE REQUIRED TO BE SIGNED, DATED AND SEALED AS
 PREVIOUSLY STATED AND REQUIRED UNDER THE FBC. PLEASE
 ALSO SEE 13-103.1.1.1 FOR REQUIRED CERTIFICATIONS.
  
 5) NOTE:SAME NOTE: PLEASE SEE A NOTE WAS ADDED FOR
 REQUIRED DEVICES; HOWEVER NO CHANGES WERE MADE TO THE
 SYMBOL LEGEND FOR TYPE? ETC.
 PLEASE SEE LS-101 16.5.1.2
 SPECIAL PROTECTIVE COVERS FOR ALL ELECTRICAL
 RECEPTACLES SHALL BE INSTALLED IN ALL AREAS OCCUPIED BY
 CLIENTS.
 PLEASE KNOW THAT THIS DOES NOT MEAN THE PLASTIC PLUG-IN
 TYPE DEVICES, THIS MEANS THE RECEPTACLE DEVICE SHALL BE
 LISTED FOR USE (110.3) AND BE OF THE TYPE WHICH
 PROVIDES AUTOMATIC PROTECTION IF AN APPLIANCE IS NOT
 PLUGGED IN OR IN USE.
  
 5) NOTE: PLEASE CLARIFY THE NEW NOTE #6 WHICH WAS ADDED
 TO PLANS. THIS NOTE AND THE CODE SECTION NOTED HAVE
 NOTHING TO DO WITH ONE ANOTHER.
 PLEASE SEE THE LS CODE STIPULATES THE MINIMUM LEVELS
 FOR EGRESS LIGHTING PER 7.8.1.3, 7.9.2.2.
 PLEASE SEE THE SECTION OF THE FBC NOTED IS FOR
 ADDITIONAL INFORMATION REQUIRED ON PLANS ONLY.
  
 6) NOTE: AS RISER HAS NOW CHANGED FROM THAT PREVIOUSLY
 SUBMITTED, PLEASE SEE THE PANEL SCHEDULE SHOWS A MCB (
 MAIN CIRCUIT BREAKER) AND THE RISER SHOWS PANEL AS
 MLO(MAIN LUG ONLY). PLEASE COORDINATE.
  
 7) NOTE: PLEASE SEE THE PLANS APPEAR TO SHOW A PANEL
 INSIDE, HOWEVER AS THE PLANS ARE NOT CLEAR, THE
 LOCATION IS NOT CONFIRMED.
 *IMPORTANT*
 PLEASE BE SURE TO SEE THE LIFE SAFETY CODE WITH RESPECT
 TO ELECTRICAL PANELS IN DAY CARE USE OCCUPANCIES.
 (PANELS REQUIRED CONTAINING LOCKABLE COVERS IF INSIDE
 BUILDING AND ACCESSIBLE FOR OCCUPANTS.
 PLEASE SEE 110.26, 240.24, 408.7, LS 101CHAPTER 6.
  
 8) NOTE:THIS IS THE SAME NOTE. THE LOAD CALCULATIONS
 SUBMITTED ARE FOR A RESIDENTIAL USE AND NOT FOR
 COMMERCIAL. PLEASE REVISE AND CORRECT.
 PLEASE SEE THE LOAD CALCULATIONS SHALL MEET 2005 NEC,
 THESE ARE SUBMITTED AND SHOWN FOR DWELLING USE AND
 OCCUPANCY.
 PLEASE SEE 220.3, 220.12, 220.14, 220.42, 220.44,
 PLEASE BE SURE ALL CONTINUOUS LOADS AT SHOWN AT 125%.
 215.3, 230.42
  
 9) NOTE: PLEASE KNOW THAT SINCE THERE ARE MANY ITEMS
 NOT YET SUBMITTED FOR REVIEW, PLEASE KNOW THAT THERE
 MAY BE NEW COMMENTS ON THE NEXT REVIEW WHICH ARE NOT
 MADE AT THIS TIME.
 PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO REPEAT
 COMMENTS FOR CODE COMPLIANCE.
  
  
 ** ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved