Plan Review Notes For Permit 07011175 |
Permit Number |
07011175 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-02-24 12:23:01 | PLAN DENIED | | PLEASE PROVIDE FRESH AIR CALCULATIONS FROM TABLE 403.4 | | 2000 FBC(M) . | | PLEASE REMOVE RETURN AIR DUCT FROM BATHROOM PER SECTION | | 601.4 #3 | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|