2007-03-08 14:08:12*****DENIED*****
  
  
 PLEASE BE ADVISED THAT THIS IS A CHANGE IN OCCUPANCY
 FROM AN EXISTING RESIDENTIAL STRUCTURE TO A NEW DAY
 CARE OCCUPANCY
  
  
  
 01.THE LIFE SAFETY CODE, NFPA 101, 2003 EDITION SHALL
 BE REFERENCED.
  
 02.PROVIDE THE OCCUPANT LOAD, IN NUMBER OF PERSONS
 FOR WHOM MEANS OF EGRESS AND OTHER PROVISIONS ARE
 REQUIRED,EITHER SHALL BE DETERMINED ON THE BASIS OF
 THE OCCUPANT LOAD FACTORS OF TABLE 7.3.1.2 THAT ARE
 CHARACTERISTIC OF THE USE OF THE SPACE OR SHALL BE
 DETERMINED AS THE MAXIMUMPROBABLE POPULATION OF THE
 SPACE UNDER CONSIDERATION, WHICHEVER IS GREATER.
  
 03.IF THE OCCUPANT LOAD IS DETERMINED BASED UPON THE
 MAXIMUM PROBABLE POPULATION OF THE SPACE, AN APPROVED
 AISLE, SEATING, AND EXITING DIAGRAM SHALL BE REQUIRED
 TO SUBSTANTIATE SUCH A MODIFICATION.
  
 04.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 05.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT
 OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 06.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF
 NEW BUILDING MATERIALS & SUPPLIES SHALL NOT INTERFERE
 OR HINDER WITH EMERGENCY RESPONSE ACCESS TO THE SAID
 PROPERTY OR VICINITY THEREOF (INCLUDING STREETS OR
 ROADWAYS).
  
 07.SHOW/DISPLAY THE NUMERICAL ADDRESS ON THE
 APPROPIATE EXTERIOR ELEVATION WHICH FRONTS 13TH STREET.
 AS PER WEST PALM BEACH CODE, THOSE NUMBERS SHALL BE NO
 LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN WIDTH
 CONTRASTING TO THE BACKGROUND.(NUMBERS SHALL NOT BE
 ON THE DOOR)
  
 08.PROVIDE A LIFE SAFETY PLAN SHEET WHICH INDICATES
 THE TRAVEL DISTANCE TO THE EXITS.THIS SHEET MAY ALSO
 INCLUDE THE LOCATION OF THE EXIT LIGHTS, EMERGENCY
 LIGHTS, FIRE ALARM DEVICES, AND THE 2A:10BC RATED FIRE
 EXTINGUISHERS APPLICABLE TO THE PROPOSED STRUCTURE.
  
 09.EVERY CLOSET DOOR LATCH SHALL BE SUCH THAT CLIENTS
 CAN OPEN THE DOOR FROM INSIDE THE CLOSET.
  
 10.EVERY BATHROOM DOOR LOCK SHALL BE DESIGNED TO
 ALLOW OPENING OF THE LOCKED DOOR FROM THE OUTSIDE BY AN
 OPENING DEVICE THAT SHALL BE READILY ACCESSSIBLE TO THE
 STAFF.
  
 11.INTERIOR WALL AND CEILING FINISH MATERIALS SHALL
 BE CLASS A OR CLASS B.
  
 12.DAY-CARE OCCUPANCIES, OTHER THAN DAY-CARE
 OCCUPANCIES HOUSED IN ONE ROOM, SHALL BE PROVIDED WITH
 A FIRE ALARM SYSTEM.
  
 13.OTHER THAN THOSE HOUSED IN ONE ROOM, A SMOKE
 DETECTION SYSTEM SHALL BE INSTALLED IN DAY-CARE
 OCCUPANCIES.
  
 14.SPECIAL PROTECTIVE COVERINGS FOR ALL ELECTRICAL
 RECEPTACLES SHALL BE INSTALLED IN ALL AREAS OCCUPIED BY
 THE CLIENTS.
  
 15.ADEQUATE ADULT STAFF SHALL BE ON DUTY, ALERT,
 AWAKE, AND IN THE FACILITY AT ALL TIMES WHERE CLIENTS
 ARE PRESENT.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 SHEET INDICATING HOW / WHERE ON THE PLANS EACH COMMENT
 WAS ADDRESSED.
  
  