Date |
Text |
2007-02-11 10:48:14 | 2007-02-11 10:48:14 |
| **** UNSAT **** |
| |
| |
| *** PLEASE SEE THAT IS A CHANGE IN OCCUPANCY TO DAY |
| CARE FACILITY. |
| |
| |
| 1) NOTE: PLEASE STATE AND DESIGN TO ALL OF THE |
| FOLLOWING MINIMUM CODES AT A MINIMUM FOR ELECTRICAL |
| REVIEW. |
| NFPA-70 2005 (2002 STATES ON PLANS), 2002 NFPA-72, 2003 |
| NFPA-101, 2004 FBC. |
| |
| ** PLEASE SEE THAT THE PLANS STATE A *LEVEL 2 |
| ALTERATION*, HOW IS THIS POSSIBLE WHEN THIS IS A CHANGE |
| IN OCCUPANCY AND ALL SHALL BE DESIGNED TO THE NEW AND |
| CURRENT CODES. |
| |
| 2) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS AND |
| CORRELATE WITH A SUBMITTED PANEL SCHEDULE WHICH IS |
| CLEAR AND VISIBLE WITH ALL INFORMATION. PLEASE SEE THE |
| PANEL SCHEDULE IS NOT CLEAR FOR ITEMS ON PANEL. PLEASE |
| CORRELATE PLANS AND PANEL SCHEDULE AS THERE ARE |
| ELECTRICAL ITEMS ON PANEL SCHEDULE WHICH ARE NOT ON |
| PLANS. |
| PLEASE SEE 700.12E FOR CIRCUITING OF EMERGENCY AND EXIT |
| LIGHTS. |
| FBC 106.1.2, 106.3.5.1.2, 106.3.1. ETC |
| NEC 408.4, 310.16, 240.4. |
| PLEASE SEE THE FOLLOWING STATEMENT WHICH IS TAKEN |
| DIRECTLY FROM THE NEC. |
| *2005 CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY |
| CIRCUIT SUPPLIED BY A PANELBOARD OR SWITCHBOARD BE |
| LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR |
| WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME |
| PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR |
| EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY |
| OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN |
| COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL |
| APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD, |
| THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL |
| RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR |
| ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.'' |
| CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH |
| ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE |
| SUFFICIENT DETAIL REQUIRED BY THIS SECTION* |
| |
| 3) NOTE: PLEASE LABEL ALL LIGHTING FIXTURES ON PLANS |
| AND CORRELATE WITH A COMPLETE FIXTURE LEGEND FOR |
| FIXTURES WHICH INDICATE TYPE AND ANY SAFETY ASPECTS FOR |
| FIXTURES (ENCLOSED LENSES ETC REQUIRED) PLEASE BE SURE |
| FIXTURES SPECIFIED MEET THE LIFE SAFETY CODE FOR DAY |
| CARE OCCUPANCIES. |
| FBC 106.1.2 LS 101 CHAPTER 16. |
| |
| 4) NOTE: PLEASE SUBMIT COMPLETE ENERGY CALCULATIONS TO |
| MEET THE 2004 FBC 13-415.1.AB.1. |
| PLEASE ALSO PROVIDE INFORMATION ON LIGHTING POWER |
| DENSITIES PER 13-415.2 |
| PLEASE SEE THAT NONE WERE SUBMITTED. |
| PLEASE ALSO SEE 13-103.1.1.1 FOR REQUIRED |
| CERTIFICATIONS. |
| |
| 5) NOTE: PLEASE SEE LS-101 16.5.1.2 |
| SPECIAL PROTECTIVE COVERS FOR ALL ELECTRICAL |
| RECEPTACLES SHALL BE INSTALLED IN ALL AREAS OCCUPIED BY |
| CLIENTS. |
| PLEASE KNOW THAT THIS DOES NOT MEAN THE PLASTIC PLUG-IN |
| TYPE DEVICES, THIS MEANS THE RECEPTACLE DEVICE SHALL BE |
| LISTED FOR USE (110.3) AND BE OF THE TYPE WHICH |
| PROVIDES AUTOMATIC PROTECTION IF AN APPLIANCE IS NOT |
| PLUGGED IN OR IN USE. |
| |
| 5) NOTE: PLEASE SEE LS 101 2003, 6.1.4.1 FOR USE, |
| 9.6.4, 16.3.4.5. |
| PLEASE SEE ALL SMOKE DETECTION DEVICES AND SYSTEM SHALL |
| BE SHOWN. |
| THIS IS NOT A RESIDENCE OR SINGLE FAMILY DWELLING. |
| |
| 6) NOTE: PLEASE SEE THAT IN NO CASE MAY THERE BE |
| *WHITE-OUT* OR HAND WRITTEN CHANGES MADE TO PLANS. |
| PLEASE ALSO SEE THAT PLANS WHICH ARE SIGNED, DATED AND |
| SEALED SHALL ALSO NOT CONTAIN THESE ITEMS. |
| FS 481.221 |
| |
| 7) NOTE: PLEASE SEE MISSING NEW FOOTER STEEL AS PART OF |
| THE GROUNDING ELECTRODE SYSTEM PER 250.50. |
| |
| 8) NOTE: PLEASE PROVIDE SCHEDULE FOR THE METER/MAIN |
| COMBO PANEL WHICH DOES NOT INDICATE ANY OVER CURRENT |
| PROTECTION DEVICES FOR ANY ITEMS FROM THE METER/MAIN. |
| PLEASE SEE THAT ANY OTHER ELECTRICAL FED ITEMS FROM THE |
| METER/MAIN PANEL SHALL ALSO BE STATED WITH THE BREAKER |
| SIZE, CONDUCTOR SIZES ETC. |
| PLEASE SHOW THE LOCATION OF ALL ELECTRICAL SERVICE |
| EQUIPMENT LOCATIONS ON ELECTRICAL PLANS. |
| PLEASE BE SURE TO SEE THE LIFE SAFETY CODE WITH RESPECT |
| TO ELECTRICAL PANELS IN DAY CARE USE OCCUPANCIES. |
| (PANELS REQUIRED TO CONTAIN LOCKABLE COVERS IF INSIDE |
| BUILDING AND ACCESSIBLE FOR OCCUPANTS. |
| PLEASE SEE 110.26, 240.24, 408.7, LS 101CHAPTER 6. |
| |
| 9) NOTE: PLEASE SEE 16.28, 16.29 FOR REQUIRED EMERGENCY |
| EGRESS LIGHTING WHICH IS REQUIRED TO MEET 7.8 AND 7.9. |
| PLEASE SEE THE MINIMUM LIGHTING LEVELS FOR EGRESS DOES |
| NOT SEEM TO BE ACCOMPLISHED AT THIS TIME FOR THE |
| LOCATION AND NUMBER OF FIXTURES SHOWN ON PLANS. PLEASE |
| SEE A MINIMUM OF 1FT CANDLE IS REQUIRED AT ALL EGRESS |
| PATHS/LEVELS OF WALKING SURFACE. |
| THIS CAN BE ACCOMPLISHED BY PROVIDING PHOTO-METRICS FOR |
| VERIFICATION OF MINIMUM LIGHTING LEVELS. |
| FBC 106.1.2 |
| |
| 10) NOTE: PLEASE PROVIDE THE SERVICE ENTRANCE |
| CONDUCTORS ON RISER. |
| 240.4, 310.16 ETC. THIS IS CONSIDERED COMMERCIAL. |
| |
| 11) NOTE: PLEASE SEE THE LOAD CALCULATIONS SHALL MEET |
| 2005 NEC, THESE ARE SUBMITTED AND SHOWN FOR DWELLING |
| USE AND OCCUPANCY. |
| PLEASE SEE 220.3, 220.12, 220.14, 220.42, 220.44, |
| PLEASE BE SURE ALL CONTINUOUS LOADS AT SHOWN AT 125%. |
| 215.3, 230.42 |
| |
| 12) NOTE: PLEASE SEE NOTE ON PLANS MENTIONS *ALL PANELS |
| (1,2 AND 3) ARE EQUIPPED WITH FUSIBLE DISCONNECT* , |
| THIS IS NOT CLEAR AS OTHER INFORMATION MENTIONS MAIN |
| CIRCUIT BREAKER EQUIPMENT. |
| PLEASE CLARIFY. |
| FBC106.1.21 |
| |
| 13) NOTE: PLEASE SEE 600.5 A AND B. |
| |
| 14) NOTE: PLEASE KNOW THAT SINCE THERE ARE MANY ITEMS |
| NOT YET SUBMITTED FOR REVIEW, PLEASE KNOW THAT THERE |
| MAY BE NEW COMMENTS ON THE NEXT REVIEW WHICH ARE NOT |
| MADE AT THIS TIME. |
| |
| |
| ** ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |