Plan Review Notes
Plan Review Notes For Permit 07011175
Permit Number 07011175
Review Stop E
Sequence Number 1
Notes
Date Text
2007-02-11 10:48:142007-02-11 10:48:14
 **** UNSAT ****
  
  
 *** PLEASE SEE THAT IS A CHANGE IN OCCUPANCY TO DAY
 CARE FACILITY.
  
  
 1) NOTE: PLEASE STATE AND DESIGN TO ALL OF THE
 FOLLOWING MINIMUM CODES AT A MINIMUM FOR ELECTRICAL
 REVIEW.
 NFPA-70 2005 (2002 STATES ON PLANS), 2002 NFPA-72, 2003
 NFPA-101, 2004 FBC.
  
 ** PLEASE SEE THAT THE PLANS STATE A *LEVEL 2
 ALTERATION*, HOW IS THIS POSSIBLE WHEN THIS IS A CHANGE
 IN OCCUPANCY AND ALL SHALL BE DESIGNED TO THE NEW AND
 CURRENT CODES.
  
 2) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS AND
 CORRELATE WITH A SUBMITTED PANEL SCHEDULE WHICH IS
 CLEAR AND VISIBLE WITH ALL INFORMATION. PLEASE SEE THE
 PANEL SCHEDULE IS NOT CLEAR FOR ITEMS ON PANEL. PLEASE
 CORRELATE PLANS AND PANEL SCHEDULE AS THERE ARE
 ELECTRICAL ITEMS ON PANEL SCHEDULE WHICH ARE NOT ON
 PLANS.
 PLEASE SEE 700.12E FOR CIRCUITING OF EMERGENCY AND EXIT
 LIGHTS.
 FBC 106.1.2, 106.3.5.1.2, 106.3.1. ETC
 NEC 408.4, 310.16, 240.4.
 PLEASE SEE THE FOLLOWING STATEMENT WHICH IS TAKEN
 DIRECTLY FROM THE NEC.
 *2005 CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY
 CIRCUIT SUPPLIED BY A PANELBOARD OR SWITCHBOARD BE
 LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR
 WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME
 PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR
 EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY
 OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN
 COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL
 APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD,
 THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL
 RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR
 ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.''
 CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH
 ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE
 SUFFICIENT DETAIL REQUIRED BY THIS SECTION*
  
 3) NOTE: PLEASE LABEL ALL LIGHTING FIXTURES ON PLANS
 AND CORRELATE WITH A COMPLETE FIXTURE LEGEND FOR
 FIXTURES WHICH INDICATE TYPE AND ANY SAFETY ASPECTS FOR
 FIXTURES (ENCLOSED LENSES ETC REQUIRED) PLEASE BE SURE
 FIXTURES SPECIFIED MEET THE LIFE SAFETY CODE FOR DAY
 CARE OCCUPANCIES.
 FBC 106.1.2 LS 101 CHAPTER 16.
  
 4) NOTE: PLEASE SUBMIT COMPLETE ENERGY CALCULATIONS TO
 MEET THE 2004 FBC 13-415.1.AB.1.
 PLEASE ALSO PROVIDE INFORMATION ON LIGHTING POWER
 DENSITIES PER 13-415.2
 PLEASE SEE THAT NONE WERE SUBMITTED.
 PLEASE ALSO SEE 13-103.1.1.1 FOR REQUIRED
 CERTIFICATIONS.
  
 5) NOTE: PLEASE SEE LS-101 16.5.1.2
 SPECIAL PROTECTIVE COVERS FOR ALL ELECTRICAL
 RECEPTACLES SHALL BE INSTALLED IN ALL AREAS OCCUPIED BY
 CLIENTS.
 PLEASE KNOW THAT THIS DOES NOT MEAN THE PLASTIC PLUG-IN
 TYPE DEVICES, THIS MEANS THE RECEPTACLE DEVICE SHALL BE
 LISTED FOR USE (110.3) AND BE OF THE TYPE WHICH
 PROVIDES AUTOMATIC PROTECTION IF AN APPLIANCE IS NOT
 PLUGGED IN OR IN USE.
  
 5) NOTE: PLEASE SEE LS 101 2003, 6.1.4.1 FOR USE,
 9.6.4, 16.3.4.5.
 PLEASE SEE ALL SMOKE DETECTION DEVICES AND SYSTEM SHALL
 BE SHOWN.
 THIS IS NOT A RESIDENCE OR SINGLE FAMILY DWELLING.
  
 6) NOTE: PLEASE SEE THAT IN NO CASE MAY THERE BE
 *WHITE-OUT* OR HAND WRITTEN CHANGES MADE TO PLANS.
 PLEASE ALSO SEE THAT PLANS WHICH ARE SIGNED, DATED AND
 SEALED SHALL ALSO NOT CONTAIN THESE ITEMS.
 FS 481.221
  
 7) NOTE: PLEASE SEE MISSING NEW FOOTER STEEL AS PART OF
 THE GROUNDING ELECTRODE SYSTEM PER 250.50.
  
 8) NOTE: PLEASE PROVIDE SCHEDULE FOR THE METER/MAIN
 COMBO PANEL WHICH DOES NOT INDICATE ANY OVER CURRENT
 PROTECTION DEVICES FOR ANY ITEMS FROM THE METER/MAIN.
 PLEASE SEE THAT ANY OTHER ELECTRICAL FED ITEMS FROM THE
 METER/MAIN PANEL SHALL ALSO BE STATED WITH THE BREAKER
 SIZE, CONDUCTOR SIZES ETC.
 PLEASE SHOW THE LOCATION OF ALL ELECTRICAL SERVICE
 EQUIPMENT LOCATIONS ON ELECTRICAL PLANS.
 PLEASE BE SURE TO SEE THE LIFE SAFETY CODE WITH RESPECT
 TO ELECTRICAL PANELS IN DAY CARE USE OCCUPANCIES.
 (PANELS REQUIRED TO CONTAIN LOCKABLE COVERS IF INSIDE
 BUILDING AND ACCESSIBLE FOR OCCUPANTS.
 PLEASE SEE 110.26, 240.24, 408.7, LS 101CHAPTER 6.
  
 9) NOTE: PLEASE SEE 16.28, 16.29 FOR REQUIRED EMERGENCY
 EGRESS LIGHTING WHICH IS REQUIRED TO MEET 7.8 AND 7.9.
 PLEASE SEE THE MINIMUM LIGHTING LEVELS FOR EGRESS DOES
 NOT SEEM TO BE ACCOMPLISHED AT THIS TIME FOR THE
 LOCATION AND NUMBER OF FIXTURES SHOWN ON PLANS. PLEASE
 SEE A MINIMUM OF 1FT CANDLE IS REQUIRED AT ALL EGRESS
 PATHS/LEVELS OF WALKING SURFACE.
 THIS CAN BE ACCOMPLISHED BY PROVIDING PHOTO-METRICS FOR
 VERIFICATION OF MINIMUM LIGHTING LEVELS.
 FBC 106.1.2
  
 10) NOTE: PLEASE PROVIDE THE SERVICE ENTRANCE
 CONDUCTORS ON RISER.
 240.4, 310.16 ETC. THIS IS CONSIDERED COMMERCIAL.
  
 11) NOTE: PLEASE SEE THE LOAD CALCULATIONS SHALL MEET
 2005 NEC, THESE ARE SUBMITTED AND SHOWN FOR DWELLING
 USE AND OCCUPANCY.
 PLEASE SEE 220.3, 220.12, 220.14, 220.42, 220.44,
 PLEASE BE SURE ALL CONTINUOUS LOADS AT SHOWN AT 125%.
 215.3, 230.42
  
 12) NOTE: PLEASE SEE NOTE ON PLANS MENTIONS *ALL PANELS
 (1,2 AND 3) ARE EQUIPPED WITH FUSIBLE DISCONNECT* ,
 THIS IS NOT CLEAR AS OTHER INFORMATION MENTIONS MAIN
 CIRCUIT BREAKER EQUIPMENT.
 PLEASE CLARIFY.
 FBC106.1.21
  
 13) NOTE: PLEASE SEE 600.5 A AND B.
  
 14) NOTE: PLEASE KNOW THAT SINCE THERE ARE MANY ITEMS
 NOT YET SUBMITTED FOR REVIEW, PLEASE KNOW THAT THERE
 MAY BE NEW COMMENTS ON THE NEXT REVIEW WHICH ARE NOT
 MADE AT THIS TIME.
  
  
 ** ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved