Plan Review Notes
Plan Review Notes For Permit 07011175
Permit Number 07011175
Review Stop B
Sequence Number 1
Notes
Date Text
2007-03-12 09:25:21BUILDING PLAN REVIEW
 PERMIT: 07011175
 ADD: 1115 13TH ST
 CONT: ALL-SITE CONSTRUCTION
 TEL: (561)317-6959
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS NULL & VOID.
 NOTE: 713.13(6)THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION
 SITE BEFORE THE FIRST INSPECTION.
  
 3 ) 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
  
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 NOTE ALSO REFLECT EXISTING BUILDING CODE 2004/2006
 AMENDMENTS
 NOTE CHAPTER 8 FOR CHANGE IN OCCUPANCY
 NOTE CHAPTER 9 FOR ADDITIONS
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.NOTE CHANGE IN
 OCCUPANCY.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
  
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 4) THE DECLARED VALUE OF THE PROJECT IS LOW IN VALUE.
 IF THE VALUE OF THE PROJECT IS NOT INCREASED,
 THE CITY WILL CALCULATE THE COST OF THE PROJECT USING
 MARSHALL & SWIFT FOR CALCULATING PURPOSES
 LATEST EDITION. 384 SQ FT X $105.10(ADDITION ALONE)=
 $40,359.00.I-4 OCCUPANCY / DAYCARE
 SEE CALCULATED FEES + STATE RADON FEES= FEE BALANCE OF
 $307.18.
  
 5) A CHANGE IN OCCUPANCY PLUS AN
 ADDITION IMPACT FEES ASSESSMENT;
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 6) PLANS INDICATE THE USE OF 32" DOORS, THE 32" POCKET
 DOORS ARE
 CODE COMPLIANTBUT THE OTHER DOORS THAT ARE A 32" DOOR
 WILL NOT PROVIDE A 32" OPENING.
 RESTROOM DOORS:11-4.22.2 DOORS.
 ALL DOORS TO ACCESSIBLE TOLIET ROOMS SHALL COMPLY WITH
 11-4.13. DOORS SHALL NOT SWING INTO
 CLEAR FLOOR SPACE REQUIRED FOR ANY
 FIXTURE.
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARANCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARANCES SHALL BE
 CLEAR & LEVEL.
  
 7) EXISTING BUILDING CODE, 812.5 ACCESSIBILITY.
 EXISTING BUILDINGS OR PORTIONS THERREOF THAT UNDERGO A
 CHANGE IN OCCUPANCY CLASSIFICATION SHALL COMPLY WITH
 CHAPTER 11 OF THE FLORIDA BUILDING CODE.
  
 8) EXISTING BUILDING CODE 905.1 ACCESSIBILITY
 PROVISIONS FOR NEW CONSTRUCTION SHALL APPLY TO
 ADDITIONS. AN ADDITION THAT AFFECTS THE ACCESSIBILITY
 TO OR CONTAIN AN AREA OF, PRIMARY FUNCTION SHALL COMPLY
 WITH THE REQUIREMENTS IN CHAPTER 11 OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 9) PLEASE PROVIDE SITE PLAN INDICATING THE HANDICAPPED
 PARKING AND ACCESSIBLE ROUTE TO THE
 ENTRY.11-4.1.1(A)(B)/ 11-4.1.2(5)(A).
  
 10)FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS
 B) EXTERIOR DOORS
 C) TRUSS ANCHORS
 D) LOUVERS
 E) ROOF ASSEMBLIES
  
 11 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
 12)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 13) PLANS DO NOT PROVIDE SLOPE OF ROOF PLEASE COMPLY
 WITH:
 1507.2.8 UNDERLAYMENT APPLICATION.
 FOR ROOF SLOPES FROM TWO UNITS VERTICAL IN 12 UNITS
 HORIZONTAL (17-PERCENT SLOPE), UP TO FOUR UNITS
 VERTICAL IN 12 UNITS HORIZONTAL (33-PERCENT SLOPE),
 UNDERLAYMENT SHALL BE TWO LAYERS APPLIED IN THE
 FOLLOWING MANNER. APPLY A MINIMUM 19-INCH-WIDE (483 MM)
 STRIP OF UNDERLAYMENT FELT PARALLEL WITH AND STARTING
 AT THE EAVES, FASTENED SUFFICIENTLY TO HOLD IN PLACE.
 STARTING AT THE EAVE, APPLY 36-INCH-WIDE (914 MM)
 SHEETS OF UNDERLAYMENT OVERLAPPING SUCCESSIVE SHEETS 19
 INCHES (483 MM) AND FASTENED SUFFICIENTLY TO HOLD IN
 PLACE. FOR ROOF SLOPES OF FOUR UNITS VERTICAL IN 12
 UNITS HORIZONTAL (33-PERCENT SLOPE) OR GREATER,
 UNDERLAYMENT SHALL BE ONE LAYER APPLIED IN THE
 FOLLOWING MANNER. UNDERLAYMENT SHALL BE APPLIED SHINGLE
 FASHION, PARALLEL TO AND STARTING FROM THE EAVE AND
 LAPPED 2 INCHES (51 MM), FASTENED ONLY AS NECESSARY TO
 HOLD IN PLACE.
  
 14) 1203.2 ATTIC SPACES.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 FRAMING MEMBERS SHALL HAVE CROSS VENTILATION FOR EACH
 SEPARATE SPACE BY VENTILATING OPENINGS PROTECTED
 AGAINST THE ENTRANCE OF RAIN. BLOCKING AND BRIDGING
 SHALL BE ARRANGED SO AS NOT TO INTERFERE WITH THE
 MOVEMENT OF AIR. A MINIMUM OF 1 INCH (25 MM) OF
 AIRSPACE SHALL BE PROVIDED BETWEEN THE INSULATION AND
 THE ROOF SHEATHING. THE NET FREE VENTILATING AREA SHALL
 NOT BE LESS THAN 1 / 150 OF THE AREA OF THE SPACE
 VENTILATED, WITH 50 PERCENT OF THE REQUIRED VENTILATING
 AREA PROVIDED BY VENTILATORS LOCATED IN THE UPPER
 PORTION OF THE SPACE TO BE VENTILATED AT LEAST 3 FEET
 (914 MM) ABOVE EAVE OR CORNICE VENTS WITH THE BALANCE
 OF THE REQUIRED VENTILATION PROVIDED BY EAVE OR CORNICE
 VENTS.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved