Plan Review Notes
Plan Review Notes For Permit 07011124
Permit Number 07011124
Review Stop M
Sequence Number 4
Notes
Date Text
2008-05-06 11:14:37REVISED PAGE M-3. SEE REDLINE NOTE ON PLANS. CLEANOUTS
 ARE REQUIRED EVERY 20 FEET IN HORIZONTAL DUCTS IN
 ACCORDANCE WITH FBCM 506.3.9 RATHER THAN AT EACH CHANGE
 IN DIRECTION AS STATED ON PLANS.