Plan Review Notes
Plan Review Notes For Permit 07011124
Permit Number 07011124
Review Stop M
Sequence Number 3
Notes
Date Text
2007-11-17 11:08:48**************PROVISO*****************
 ACCESS PANELS FOR CLEAN-OUTS IN HORIZONTAL GREASE DUCTS
 SHALL BE SPACED NOT MORE THAN 20 FEET APART IN
 ACCORDANCE WITH FBC,M 506.3.9, NOT ONLY AT CHANGES OF
 DIRECTION AS INDICATED ON PG M-3.
  