Date |
Text |
2007-08-23 08:50:48 | REVIEW #: 2ND |
| ACTION: DENIED |
| |
| FBC 2004 CODE FAMILY W/ 2005 AND 2006 REVISIONS FBC |
| CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| |
| THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| PREVIOUS REVIEW COMMENTS AS WELL AS THE DESIGNER'S |
| WRITTEN RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| |
| 1. OK |
| |
| 2. OK |
| |
| 3. THERE WAS NO WRITTEN RESPONSE TO THIS COMMENT |
| PROVIDED AND NO CHANG SHOWN ON PLANS. PLEASE SHOW HOW |
| THIS ITEM IS TO BE ADDRESSED AND RESUBMIT. |
| |
| 4. THERE IS NO FIRE DAMPER SHOWN ON 20 INCH ROUND DUCT |
| PENETRATING THE RATED TEMPORARY BARRIER. SHOW OPENING |
| PROTECTIVES PER FBC,M 607.5. |
| |
| 5. OK |
| |
| 6. OK |
| |
| 7. THERE WERE NO SPECIFICATIONS SUBMITTED WITH PLANS |
| FOR THIS REVIEW. PLEASE INCLUDE THIS INFORMATION ON THE |
| PLANS. SEE FBC 106.1.1 |
| |
| 8. THERE WERE NO SPECIFICATIONS SUBMITTED WITH PLANS |
| FOR THIS REVIEW. HOWEVER, THE RELEVANT INFORMATION HAS |
| BEEN ADDED TO THE PLANS. THIS COMMENT HAS BEEN |
| ADEQUATELY ADDRESSED. |
| |
| 9. THERE WERE NO SPECIFICATIONS SUBMITTED WITH PLANS |
| FOR THIS REVIEW. NOTE 18 ON PG M-3 CALLS FOR DUCT TO BE |
| SLOPED AT MIN. 1 INCH PER FOOT. IS THIS INTENTIONAL |
| BECAUSE THE HORIZONTAL DUCT MAY BE IN EXCESS OF 75 |
| FEET? THE 9X9 DUCT FOR HOOD #7 WOULD HAVE A RISE OF |
| MORE THAN 4 FEET BEFORE IT REACHES THE LARGER DUCT. |
| PLEASE VERIFY THAT THIS IS EVEN FEASIBLE WITH FIELD |
| CONDITIONS. |
| |
| 10. THERE WERE NO SPECIFICATIONS SUBMITTED WITH PLANS |
| FOR THIS REVIEW. ALSO, THERE ARE NO CLEANOUTS SHOWN ON |
| THE 9X9 GREASE DUCT. PLEASE CORRECT AND RESUBMIT. |
| |
| 11. OK |
| |
| 12. OK |
| |
| 13. PLEASE INDICATE ON PLANS HOW THE ADDED FIRE/SMOKE |
| DAMPERS ARE TO BE ACTUATED IN ACCORDANCE WITH FBC,M |
| 607.5.4.1. |
| |
| 14. DRAWING S-1 ATTACHED TO FRONT OF PLANS: PROVIDE TWO |
| SETS WITH ORIGINAL SEAL AND DATE/SIGNATURE PER FAC |
| 61G15-23.002 |
| |
| NEW COMMENT: THERE HAS BEEN A CHANGE OF CONTRACTOR FORM |
| FILED WITH A NEW PERMIT APPPLICATION FOR JP HURBON, |
| INC. HOWEVER, ONE OF THE SUBCONTRACTORS HAS ALSO BEEN |
| CHANGED ON THE PERMIT APPLICATION FROM BRADLEY HEATING |
| AND AIR CONDITIONING, INC. TO FARMER & IRWIN CORP. AN |
| ADDITIONAL CHANGE OF CONTRACTOR FORM MUST BE FILED TO |
| FACILITATE THIS CHANGE. |
| |