Plan Review Notes
Plan Review Notes For Permit 07011124
Permit Number 07011124
Review Stop M
Sequence Number 2
Notes
Date Text
2007-08-23 08:50:48REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 REVISIONS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS THE DESIGNER'S
 WRITTEN RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. OK
  
 2. OK
  
 3. THERE WAS NO WRITTEN RESPONSE TO THIS COMMENT
 PROVIDED AND NO CHANG SHOWN ON PLANS. PLEASE SHOW HOW
 THIS ITEM IS TO BE ADDRESSED AND RESUBMIT.
  
 4. THERE IS NO FIRE DAMPER SHOWN ON 20 INCH ROUND DUCT
 PENETRATING THE RATED TEMPORARY BARRIER. SHOW OPENING
 PROTECTIVES PER FBC,M 607.5.
  
 5. OK
  
 6. OK
  
 7. THERE WERE NO SPECIFICATIONS SUBMITTED WITH PLANS
 FOR THIS REVIEW. PLEASE INCLUDE THIS INFORMATION ON THE
 PLANS. SEE FBC 106.1.1
  
 8. THERE WERE NO SPECIFICATIONS SUBMITTED WITH PLANS
 FOR THIS REVIEW. HOWEVER, THE RELEVANT INFORMATION HAS
 BEEN ADDED TO THE PLANS. THIS COMMENT HAS BEEN
 ADEQUATELY ADDRESSED.
  
 9. THERE WERE NO SPECIFICATIONS SUBMITTED WITH PLANS
 FOR THIS REVIEW. NOTE 18 ON PG M-3 CALLS FOR DUCT TO BE
 SLOPED AT MIN. 1 INCH PER FOOT. IS THIS INTENTIONAL
 BECAUSE THE HORIZONTAL DUCT MAY BE IN EXCESS OF 75
 FEET? THE 9X9 DUCT FOR HOOD #7 WOULD HAVE A RISE OF
 MORE THAN 4 FEET BEFORE IT REACHES THE LARGER DUCT.
 PLEASE VERIFY THAT THIS IS EVEN FEASIBLE WITH FIELD
 CONDITIONS.
  
 10. THERE WERE NO SPECIFICATIONS SUBMITTED WITH PLANS
 FOR THIS REVIEW. ALSO, THERE ARE NO CLEANOUTS SHOWN ON
 THE 9X9 GREASE DUCT. PLEASE CORRECT AND RESUBMIT.
  
 11. OK
  
 12. OK
  
 13. PLEASE INDICATE ON PLANS HOW THE ADDED FIRE/SMOKE
 DAMPERS ARE TO BE ACTUATED IN ACCORDANCE WITH FBC,M
 607.5.4.1.
  
 14. DRAWING S-1 ATTACHED TO FRONT OF PLANS: PROVIDE TWO
 SETS WITH ORIGINAL SEAL AND DATE/SIGNATURE PER FAC
 61G15-23.002
  
 NEW COMMENT: THERE HAS BEEN A CHANGE OF CONTRACTOR FORM
 FILED WITH A NEW PERMIT APPPLICATION FOR JP HURBON,
 INC. HOWEVER, ONE OF THE SUBCONTRACTORS HAS ALSO BEEN
 CHANGED ON THE PERMIT APPLICATION FROM BRADLEY HEATING
 AND AIR CONDITIONING, INC. TO FARMER & IRWIN CORP. AN
 ADDITIONAL CHANGE OF CONTRACTOR FORM MUST BE FILED TO
 FACILITATE THIS CHANGE.
  