Plan Review Notes For Permit 07011124 |
Permit Number |
07011124 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-09-07 15:16:31 | ***DENIED*** | | A RESPONSE LETTER WAS INCLUDED ADDRESSING OTHER REVIEW | | COMMENTS. IT WOULD HELP EXPEDITE THIS PROCESS IF A | | LETTER ADDRESSING FIRE REVIEW COMMENTS WAS PROVIDED | | INDICATING WHERE INFORMATION MAY BE FOUND IF CORRECTED | | ON PLANS. | | | | 1) THE APPLICATION INDICATES KITCHEN HOOD REPLACEMENT | | AND THE NARRATIVE ON SHT X1.1 MENTIONS FIRE SUPPRESSION | | SYSTEM. DOES THE SYSTEM CURRENTLY MEET THE REQUIREMENTS | | FOR A WET CHEMICAL UL 300 APPLICATION, OR WILL IT BE | | UPGRADED DURING THE SCOPE OF THIS WORK? | | | | 2) PLEASE SHOW LOCATION OF REQUIRED "K" FIRE | | EXTINGUISHER. | | | | 3) IN ADDITION TO LISTED CODES, CONSTRUCTION, | | ALTERATION AND DEMOLITION SHALL COMPLY WITH NFPA 241. | | | | 4) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR HOOD | | AND FIRE SUPPRESSION SYSTEMS. | | | | 5) WORK SHALL NOT INTERFERE WITH EXISTING BUILDING FIRE | | PROTECTION EQUIPMENT AND REQUIRED MEANS OF EGRESS. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW(561) 805-6722 | | FIRE PREVENTION(561) 804-4756 |
|