2007-02-04 18:55:42** UNSAT **
  
 1) NOTE: PLEASE SEE THE CODES ADOPTED AND IN DESIGN
 SHALL BE STATED ON THE PLANS.
 PLEASE KNOW THAT AS OF DECEMBER 8TH, 2006 THE STATE OF
 FLORIDA ADOPTED THE 2006 REVISIONS TO THE 2004 FBC AND
 THE 2005 NFPA-70.
 PLEASE BE SURE TO STATE THE FOLLOWING ON THE PLANS AT A
 MINIMUM AND ANY OTHERS WHICH MAY BE MENTIONED BY OTHER
 TRADES.
 2004 FBC W/2006 (REVISIONS)
 2005 NFPA-70 NEC.
  
 2) NOTE: PLEASE SUBMIT PANEL SCHEDULE FOR NEW
 CIRCUIT(S) LOADS ON NEW AND EXISTING. PLEASE SHOW THE
 CONDUCTOR SIZE(S), OVER CURRENT PROTECTION ETC.
 408.4, 310.16, 240.4.
 PLEASE INDICATE ANY CONTINUOUS LOADS AT 125% 215.3,
 230.42/ MOTOR LOADS?
  
 3) NOTE: PLEASE INDICATE NEW OR EXISTING SHUNT/SHUT
 DOWN OF ALL ELECTRICAL UNDER HOOD PER NFPA-96.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  