2007-02-04 18:55:42 | ** UNSAT ** |
| |
| 1) NOTE: PLEASE SEE THE CODES ADOPTED AND IN DESIGN |
| SHALL BE STATED ON THE PLANS. |
| PLEASE KNOW THAT AS OF DECEMBER 8TH, 2006 THE STATE OF |
| FLORIDA ADOPTED THE 2006 REVISIONS TO THE 2004 FBC AND |
| THE 2005 NFPA-70. |
| PLEASE BE SURE TO STATE THE FOLLOWING ON THE PLANS AT A |
| MINIMUM AND ANY OTHERS WHICH MAY BE MENTIONED BY OTHER |
| TRADES. |
| 2004 FBC W/2006 (REVISIONS) |
| 2005 NFPA-70 NEC. |
| |
| 2) NOTE: PLEASE SUBMIT PANEL SCHEDULE FOR NEW |
| CIRCUIT(S) LOADS ON NEW AND EXISTING. PLEASE SHOW THE |
| CONDUCTOR SIZE(S), OVER CURRENT PROTECTION ETC. |
| 408.4, 310.16, 240.4. |
| PLEASE INDICATE ANY CONTINUOUS LOADS AT 125% 215.3, |
| 230.42/ MOTOR LOADS? |
| |
| 3) NOTE: PLEASE INDICATE NEW OR EXISTING SHUNT/SHUT |
| DOWN OF ALL ELECTRICAL UNDER HOOD PER NFPA-96. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |