Plan Review Notes
Plan Review Notes For Permit 07011115
Permit Number 07011115
Review Stop B
Sequence Number 3
Notes
Date Text
2007-04-02 09:05:16****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 1.)ADDRESSED.
  
 2.)ADDRESSED.
  
 3.)IN SEVERAL PLACES, THE PLAN STATES "AS PER FBC
 2004 1009".DETAILS ARE TO BE SPECIFIC FBC*106.1.1.
  
 DETAILS ARE NOW PROVIDED BUT ARE NOT CODE COMPLIANT;
 SEE OTHER COMMENTS.
  
 4.)PROVIDE A PERMIT NUMBER FOR WHAT YOU CALL
 "EXISTING STAIRS" ON THE PLAN.THE DIMENSIONS ARE TO
 COMPLY WITH FBC1009.ON THE PLAN, EVERY RISER IS SHOWN
 AT A DIFFERENT DIMENSION RANGING FROM 2" TO 6" ON ONE
 SIDE, 5" AND 7" ON THE OTHER SIDE, AND THE TREADS ARE
 SHOWN AT 2'11" AND 3'2".SEE FBC1009.3.IT APPEARS
 THAT THE "EXISTING STAIRS" WERE NOT BUILT IN COMPLIANCE
 WITH THE CURRENT BUILDING CODE AND PRESENT A HAZARD.
  
 2ND REVIEW, A "STEPS REPAIR" WAS INCLUDED IN THE PLAN,
 AND NOW THERE ARE RISER HEIGHTS RANGING FROM 4.5" TO
 6".PLEASE READ REFERENCED CODE SECTION AND REVISE.
 STAIRS MODIFIED AS PROPOSED ARE NOT CODE COMPLIANT AND
 STILL PRESENT A HAZARD.
  
 5.)DECLARE GOVERNING CODE, INCLUDING 2006 AMENDMENTS,
 AND EXISTING BUILDING CODE.
  
 NOT ADDRESSED.
  
 6.)IS THIS A CHANGE OF OCCUPANCY?OUR RECORDS SHOW
 AN AUTO BODY SHOP IN THIS LOCATION.
  
 NOT ADDRESSED.PROVIDING A SITE PLAN DOES NOT SHOW
 COMPLIANCE.OCCUPANCY CLASSIFICATIONS ARE TO BE
 DECLARED AS IN FBC CHAPTER 3.THE SITE PLAN AND SURVEY
 SHOW TWO SEPARATE BUILDINGS 6' APART.IT IS NOT CLEAR
 IF AN OCCUPANCY WAS CHANGED WITHOUT SHOWING COMPLIANCE
 WITH FBC6 AND FBC5.TWO TENANTS ARE SHOWN IN ONE
 BUILDING, BUT THIS DOES NOT ANSWER THE QUESTION IN
 REGARDS TO THE CHANGE OF OCCUPANCY.
  
 7.)THE GUARD IS TO COMPLY WITH FBC1012 AND FBC1607.7.
 SHOW COMPLIANCE ON THE PLAN.
  
 PROVIDE CALUCLATIONS; IT IS NOT CLEAR IF THE WOOD 1X2
 PICKETS WILL WITHSTAND LOADS FBC1607.7.1.2.THIS
 SECTION WAS NOT MENTIONED IN THE DESIGN CRITERIA.
  
 8.)ADDRESSED.
  
 9.)THE CONTRACTOR DECLARED A $350 VALUE.PROVIDE A
 REASONABLE VALUE OR A VALUATION ADJUSTMENT WILL BE DONE
 FOR YOU USING MARSHALL & SWIFT.
  
 CONTRACTOR HAS REVISED THE COST.THIS WILL BE
 EVALUATED AFTER THE COMPLETE SCOPE OF WORK HAS BEEN
 DETERMINED.
  
 10.)HANDRAILS REQUIRED ON BOTH SIDES OF THE STAIR,
 FBC1009.11.SHOW ALL DETAILS TO SHOW COMPLIANCE WITH
 FBC11-4.9.4 AND FBC1009.
  
 NO HANDRAILS SHOWN.
  
 11.)ADDRESSED.
  
 12.)DIAZ DRAFTING SERVICES HAS ALREADY BEEN INFORMED
 BY THIS DEPARTMENT THAT THEY ARE NOT LICENSED TO DO
 DESIGN WORK FOR COMMERCIAL PROPERTIES.CONTINUED
 NONCOMPLIANCE WILL RESULT IN A COMPLAINT AGAINST THE
 COMPANY.DUE TO THIS ISSUE AND THE DEFICIENCIES IN THE
 PLAN, A SET HAS BEEN RETAINED.
  
 A SET OF THE PLANS IS TO BE SENT TO FBPE AS PREVIOUSLY
 ADVISED.
  
 13.)THE NOTES STATE THAT THE BOTTOM RAIL SHALL REJECT
 THE PASSAGE OF A 2" OBJECT.HOWEVER, A 3" AND 5" GAP
 IS SHOWN BETWEEN THE BOTTOM OF THE BALUSTERS AND THE
 "PLATFORM".DETAILS ARE TO BE CONSISTENT AND CODE
 COMPLIANT.SEE FBC1012.
  
 NOT ADDRESSED.
  
 NEW COMMENTS:
  
 14.)RENAMING THE NONCOMPLIANT STAIRS TO "STEPS" DOES
 NOT ELIMINATE THE REQUIREMENTS FOR STAIRS.REGARDLESS
 OF WHAT YOU CALL THEM, THEY ARE STAIRS FBC1002
 DEFININTIONS, AND ARE TO COMPLY WITH FBC1009.
  
 15.)INCLUDE A RESPONSE LETTER WITH THE RESUBMITTAL,
 PREPARED BY THE DESIGNER OF RECORD.
  
 16.)SEE ATTACHED FS553.80(2)(B).