Date |
Text |
2007-04-02 09:05:16 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC |
| FLORIDA ADMINISTRATIVE CODE |
| FSFLORIDA STATUTE |
| |
| FROM PREVIOUS LIST: |
| |
| 1.)ADDRESSED. |
| |
| 2.)ADDRESSED. |
| |
| 3.)IN SEVERAL PLACES, THE PLAN STATES "AS PER FBC |
| 2004 1009".DETAILS ARE TO BE SPECIFIC FBC*106.1.1. |
| |
| DETAILS ARE NOW PROVIDED BUT ARE NOT CODE COMPLIANT; |
| SEE OTHER COMMENTS. |
| |
| 4.)PROVIDE A PERMIT NUMBER FOR WHAT YOU CALL |
| "EXISTING STAIRS" ON THE PLAN.THE DIMENSIONS ARE TO |
| COMPLY WITH FBC1009.ON THE PLAN, EVERY RISER IS SHOWN |
| AT A DIFFERENT DIMENSION RANGING FROM 2" TO 6" ON ONE |
| SIDE, 5" AND 7" ON THE OTHER SIDE, AND THE TREADS ARE |
| SHOWN AT 2'11" AND 3'2".SEE FBC1009.3.IT APPEARS |
| THAT THE "EXISTING STAIRS" WERE NOT BUILT IN COMPLIANCE |
| WITH THE CURRENT BUILDING CODE AND PRESENT A HAZARD. |
| |
| 2ND REVIEW, A "STEPS REPAIR" WAS INCLUDED IN THE PLAN, |
| AND NOW THERE ARE RISER HEIGHTS RANGING FROM 4.5" TO |
| 6".PLEASE READ REFERENCED CODE SECTION AND REVISE. |
| STAIRS MODIFIED AS PROPOSED ARE NOT CODE COMPLIANT AND |
| STILL PRESENT A HAZARD. |
| |
| 5.)DECLARE GOVERNING CODE, INCLUDING 2006 AMENDMENTS, |
| AND EXISTING BUILDING CODE. |
| |
| NOT ADDRESSED. |
| |
| 6.)IS THIS A CHANGE OF OCCUPANCY?OUR RECORDS SHOW |
| AN AUTO BODY SHOP IN THIS LOCATION. |
| |
| NOT ADDRESSED.PROVIDING A SITE PLAN DOES NOT SHOW |
| COMPLIANCE.OCCUPANCY CLASSIFICATIONS ARE TO BE |
| DECLARED AS IN FBC CHAPTER 3.THE SITE PLAN AND SURVEY |
| SHOW TWO SEPARATE BUILDINGS 6' APART.IT IS NOT CLEAR |
| IF AN OCCUPANCY WAS CHANGED WITHOUT SHOWING COMPLIANCE |
| WITH FBC6 AND FBC5.TWO TENANTS ARE SHOWN IN ONE |
| BUILDING, BUT THIS DOES NOT ANSWER THE QUESTION IN |
| REGARDS TO THE CHANGE OF OCCUPANCY. |
| |
| 7.)THE GUARD IS TO COMPLY WITH FBC1012 AND FBC1607.7. |
| SHOW COMPLIANCE ON THE PLAN. |
| |
| PROVIDE CALUCLATIONS; IT IS NOT CLEAR IF THE WOOD 1X2 |
| PICKETS WILL WITHSTAND LOADS FBC1607.7.1.2.THIS |
| SECTION WAS NOT MENTIONED IN THE DESIGN CRITERIA. |
| |
| 8.)ADDRESSED. |
| |
| 9.)THE CONTRACTOR DECLARED A $350 VALUE.PROVIDE A |
| REASONABLE VALUE OR A VALUATION ADJUSTMENT WILL BE DONE |
| FOR YOU USING MARSHALL & SWIFT. |
| |
| CONTRACTOR HAS REVISED THE COST.THIS WILL BE |
| EVALUATED AFTER THE COMPLETE SCOPE OF WORK HAS BEEN |
| DETERMINED. |
| |
| 10.)HANDRAILS REQUIRED ON BOTH SIDES OF THE STAIR, |
| FBC1009.11.SHOW ALL DETAILS TO SHOW COMPLIANCE WITH |
| FBC11-4.9.4 AND FBC1009. |
| |
| NO HANDRAILS SHOWN. |
| |
| 11.)ADDRESSED. |
| |
| 12.)DIAZ DRAFTING SERVICES HAS ALREADY BEEN INFORMED |
| BY THIS DEPARTMENT THAT THEY ARE NOT LICENSED TO DO |
| DESIGN WORK FOR COMMERCIAL PROPERTIES.CONTINUED |
| NONCOMPLIANCE WILL RESULT IN A COMPLAINT AGAINST THE |
| COMPANY.DUE TO THIS ISSUE AND THE DEFICIENCIES IN THE |
| PLAN, A SET HAS BEEN RETAINED. |
| |
| A SET OF THE PLANS IS TO BE SENT TO FBPE AS PREVIOUSLY |
| ADVISED. |
| |
| 13.)THE NOTES STATE THAT THE BOTTOM RAIL SHALL REJECT |
| THE PASSAGE OF A 2" OBJECT.HOWEVER, A 3" AND 5" GAP |
| IS SHOWN BETWEEN THE BOTTOM OF THE BALUSTERS AND THE |
| "PLATFORM".DETAILS ARE TO BE CONSISTENT AND CODE |
| COMPLIANT.SEE FBC1012. |
| |
| NOT ADDRESSED. |
| |
| NEW COMMENTS: |
| |
| 14.)RENAMING THE NONCOMPLIANT STAIRS TO "STEPS" DOES |
| NOT ELIMINATE THE REQUIREMENTS FOR STAIRS.REGARDLESS |
| OF WHAT YOU CALL THEM, THEY ARE STAIRS FBC1002 |
| DEFININTIONS, AND ARE TO COMPLY WITH FBC1009. |
| |
| 15.)INCLUDE A RESPONSE LETTER WITH THE RESUBMITTAL, |
| PREPARED BY THE DESIGNER OF RECORD. |
| |
| 16.)SEE ATTACHED FS553.80(2)(B). |