Plan Review Notes
Plan Review Notes For Permit 07011115
Permit Number 07011115
Review Stop B
Sequence Number 2
Notes
Date Text
2007-03-06 17:12:23****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)DO NOT REFER TO THE "TYPICAL NOTES" TO SHOW CODE
 COMPLIANCE AS YOUR NOTES ARE CONFLICTING AND ARE NOT
 CODE COMPLIANT.
  
 2.)NOTE 6 STATES THAT STAIRS GUARDRAILS TO BE 34" TO
 38" HIGH, NOTE 4 STATES THAT GUARDRAILS ARE TO BE 42"
 HIGH.
  
 3.)IN SEVERAL PLACES, THE PLAN STATES "AS PER FBC
 2004 1009".DETAILS ARE TO BE SPECIFIC FBC*106.1.1.
  
 4.)PROVIDE A PERMIT NUMBER FOR WHAT YOU CALL
 ?EXISTING STAIRS? ON THE PLAN.THE DIMENSIONS ARE TO
 COMPLY WITH FBC1009.ON THE PLAN, EVERY RISER IS SHOWN
 AT A DIFFERENT DIMENSION RANGING FROM 2? TO 6? ON ONE
 SIDE, 5? AND 7? ON THE OTHER SIDE, AND THE TREADS ARE
 SHOWN AT 2?11? AND 3?2?.SEE FBC1009.3.IT APPEARS
 THAT THE ?EXISTING STAIRS? WERE NOT BUILT IN COMPLIANCE
 WITH THE CURRENT BUILDING CODE AND PRESENT A HAZARD.
  
 5.)DECLARE GOVERNING CODE, INCLUDING 2006 AMENDMENTS,
 AND EXISTING BUILDING CODE.
  
 6.)IS THIS A CHANGE OF OCCUPANCY?OUR RECORDS SHOW
 AN AUTO BODY SHOP IN THIS LOCATION.
  
 7.)THE GUARD IS TO COMPLY WITH FBC1012 AND FBC1607.7.
 SHOW COMPLIANCE ON THE PLAN.
  
 8.)MANY PLACES ON THE PLAN STATE "BY OTHERS".WHAT
 DOES THIS MEAN?PLANS ARE TO SHOW CODE COMPLIANCE AND
 SCOPE OF WORK.APPLICATION STATES "ADD GUARD RAIL TO
 EXISTING CONCRETE WALKWAY AND LEVEL IT."HOW CAN YOU
 EXCLUDE THE GUARDRAIL IF THAT'S THE PURPOSE OF THE
 APPLICATION?WHERE IS THE CONCRETE WALKWAY?WHAT DOES
 "LEVEL IT" MEAN?PLANS SHOULD CLEARLY SHOW SCOPE OF
 WORK AND BE CONSISTENT WITH THE APPLICATION.
  
 9.)THE CONTRACTOR DECLARED A $350 VALUE.PROVIDE A
 REASONABLE VALUE OR A VALUATION ADJUSTMENT WILL BE DONE
 FOR YOU USING MARSHALL & SWIFT.
  
 10.)HANDRAILS REQUIRED ON BOTH SIDES OF THE STAIR,
 FBC1009.11.SHOW ALL DETAILS TO SHOW COMPLIANCE WITH
 FBC11-4.9.4 AND FBC1009.
  
 11.)THE PLANS STATE ?PRE-FABRIC. GUARDRAIL PER 1108.5
 FBC SEE TYPICAL NOTES BY OTHERS.?WHAT IS BY OTHERS,
 THE TYPICAL NOTES OR THE GUARDRAIL?SEE COMMENT 8
 ABOVE REGARDING WHAT INFORMATION IS REQUIRED TO BE ON
 THE PLAN.SECTION 1108.5 DOES NOT EXIST IN THE FLORIDA
 BUILDING CODE, NOT SURE OF THE PURPOSE OF THIS NOTE.
  
 12.)DIAZ DRAFTING SERVICES HAS ALREADY BEEN INFORMED
 BY THIS DEPARTMENT THAT THEY ARE NOT LICENSED TO DO
 DESIGN WORK FOR COMMERCIAL PROPERTIES.CONTINUED
 NONCOMPLIANCE WILL RESULT IN A COMPLAINT AGAINST THE
 COMPANY.DUE TO THIS ISSUE AND THE DEFICIENCIES IN THE
 PLAN, A SET HAS BEEN RETAINED.
  
 13.)THE NOTES STATE THAT THE BOTTOM RAIL SHALL REJECT
 THE PASSAGE OF A 2" OBJECT.HOWEVER, A 3" AND 5" GAP
 IS SHOWN BETWEEN THE BOTTOM OF THE BALUSTERS AND THE
 "PLATFORM".DETAILS ARE TO BE CONSISTENT AND CODE
 COMPLIANT.SEE FBC1012.
  