Plan Review Notes For Permit 07011091 |
Permit Number |
07011091 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-01-31 14:15:47 | *** DENIED *** | | 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | ALSO, PER 2004 FBC 13-600.3.ABC.2. | | | | 2) PLEASE SHOW SIZE OF SUPPLY AIR TRUNK LINE TO BEDROOM | | ON MECHANICAL PLANS. | | | | 3) IF THE AIR FILTER IS NOT AT THE AHU BUT AT THE 24X12 | | RETURN AIR GRILL THEN THE 8X6 RETURN AIR GRILL IN THE | | BEDROOM WILL NEED A FILTER ALSO, PLEASE STATE AIR | | FILTER LOCATION ON MECH. PLANS. | | | | 4) 4X12 RETURN AIR TRANSFER GRILL TO BEDROOM IS TO | | SMALL FOR 200 CFM'S.BALANCED RETURN AIR MAY BE | | ACHIEVED BY. | | (B)TRANSFER GRILLES SHALL USE 50 | | SQUARE INCHES (OF GRILLE AREA) TO 100 | | CFM (OF SUPPLY AIR) FOR SIZING | | THROUGH-THE-WALL TRANSFER GRILLES AND | | USING AN UNRESTRICTED 1-INCH | | UNDERCUTTING OF DOORS TO ACHIEVE PROPER | | RETURN AIR BALANCE. PER 2004 FBC/R M1602.4 . | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|