Plan Review Notes For Permit 07011091 |
Permit Number |
07011091 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-01-30 10:54:22 | | | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | 1} PER 110.9 AND 110.10: OBTAIN THE | | AVAILABLE FAULT CURRENT AT THE UTILITY | | AND CALCULATE THE SAME AT THE EQUIPMENT. | | INDICATE THE AIC RATING FOR THE | | EQUIPMENT IS EQUAL TO OR GREATER THAN | | THE AVAILABLE FAULT. | | | | 2} PLEASE INDICATE THE SIZE AND TYPE RACEWAY TO BE USED | | FOR THE SERVICE RISER AND PANEL FEEDER. | | | | 3} PLEASE IDENTIFY THE 4/0 SERVICE CABLE FEEDING THE | | PANEL. (IG: SE). | | | | 4} THE BATH CIRCUIT ,#6, ON THE SCHEDULE MUST BE 20 AMP | | TO COMPLY WITH 210.11(C)(3) AND 310.16. | | | | 5} THE DINING ROOM MUST BE ON A SMALL APPLIANCE CIRCUIT | | , OR ITS OWN 20 AMP CIRCUIT PER 210.52(B). | | | | 6} CIRCUIT #3 FEEDING THE SMOKE ALARMS MUST BE AFCI PER | | 210.12. | | | | 7} BOTH BEDROOMS MUST HAVE RECEPTACLES ADDED TO COMPLY | | WITH THE SPACING REQUIREMENTS OF 210.52(A)(1) AND (2). | | SEE REVIEWED SET OF PLANS. | | | | 8} NOTE THATTHE REQUIRED RECEPTACLE PER 210.63. LIGHT | | PER 210.70(A) (3),MUST BE INSTALLED FOR THE AIR | | HANDLER IN THE ATTIC. | | | | 9} THE WATER HEATER IS SHOWN AS BEING PLUGGED INTO A | | RECEPTACLE. PLEASE SEE 422.16 FOR CORD AND PLUG | | ATTACHED APPLIANCES RESTRICIION. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW. | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|