Plan Review Notes
Plan Review Notes For Permit 07011091
Permit Number 07011091
Review Stop E
Sequence Number 1
Notes
Date Text
2007-01-30 10:54:22 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 2} PLEASE INDICATE THE SIZE AND TYPE RACEWAY TO BE USED
 FOR THE SERVICE RISER AND PANEL FEEDER.
  
 3} PLEASE IDENTIFY THE 4/0 SERVICE CABLE FEEDING THE
 PANEL. (IG: SE).
  
 4} THE BATH CIRCUIT ,#6, ON THE SCHEDULE MUST BE 20 AMP
 TO COMPLY WITH 210.11(C)(3) AND 310.16.
  
 5} THE DINING ROOM MUST BE ON A SMALL APPLIANCE CIRCUIT
 , OR ITS OWN 20 AMP CIRCUIT PER 210.52(B).
  
 6} CIRCUIT #3 FEEDING THE SMOKE ALARMS MUST BE AFCI PER
 210.12.
  
 7} BOTH BEDROOMS MUST HAVE RECEPTACLES ADDED TO COMPLY
 WITH THE SPACING REQUIREMENTS OF 210.52(A)(1) AND (2).
 SEE REVIEWED SET OF PLANS.
  
 8} NOTE THATTHE REQUIRED RECEPTACLE PER 210.63. LIGHT
 PER 210.70(A) (3),MUST BE INSTALLED FOR THE AIR
 HANDLER IN THE ATTIC.
  
 9} THE WATER HEATER IS SHOWN AS BEING PLUGGED INTO A
 RECEPTACLE. PLEASE SEE 422.16 FOR CORD AND PLUG
 ATTACHED APPLIANCES RESTRICIION.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.