2007-02-21 08:43:51DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR THE SEPARATE GAS PERMIT:
  
 1. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
  
 2. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 THE BTU INFORMATION SUBMITTED IS CONFLICTING FROM ONE
 PAGE TO THE OTHER. THE NEXT TO LAST SHEET INDICATES THE
 BTU LOAD TO BE 905,000 BTU'S, BUT THE FINAL PAGE
 INDICATES FUEL CONSUMPTION TO BE 4200 CFH, (4,536,000
 BTU'S). PLEASE CLARIFY AS THIS IS A LARGE DISCREPENCY.
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 4. THE PERSON RESPONSIBLE FOR THE DESIGN OF THE PIPING
 SHALL PRINT THEIR NAME AND SIGN THE PLANS. SECTION
 106.1.
  
 5. PER TABLE 402.4.3 THE PIPING FOR 905,000 BTU AT 150
 FEET SHALL BE A MINIMUM 1" PIPE. IF THE MAXIMUM BTU
 LOAD IS 4,536,000 BTU AS INDICATED ON THE LAST PAGE OF
 THE SUBMITTAL, THEN THE PIPE SIZE SHALL BE 1-1/2".
  
 6. PLEASE INDICATE THE MODEL NUMBER OF THE REGULATOR TO
 BE USED. KEEP IN MIND THE MANUF. RECOMMENDATION THAT
 THE REGULATOR IS WITHIN ONE SIZE OF THE MANIFOLD PIPE
 SIZE. SECTION 106.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]