Plan Review Notes
Plan Review Notes For Permit 07011081
Permit Number 07011081
Review Stop B
Sequence Number 1
Notes
Date Text
2007-02-16 08:36:19BUILDING PLAN REVIEW
 PERMIT: 07011081
 ADD:3501 S.DIXIE HWY
 CONT: SIGN CRAFT
 TEL: (561)863-3660
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST.
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)106.1.1CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. THE CALCULATIONS
 SUBMITTED FOR THE THE SING STRUCTURE IS NOT LEGIBLE.
  
 3)471.025ALLFINAL DRAWINGS, SPECIFICATIONS,
 PLANS, REPORTS, OR DOCUMENTS PREPARED OR ISSUED BY THE
 LICENSEE AND BEING FILED FOR PUBLIC RECORD AND ALL
 FINAL DOCUMENTS PROVIDED TO THE OWNER OR THE OWNER'S
 REPRESENTATIVE SHALL BE SIGNED BY THE LICENSEE, DATED,
 AND SEALED WITH SAID SEAL. SUCH SIGNATURE, DATE, AND
 SEAL SHALL BE EVIDENCE OF THE AUTHENTICITY OF THAT TO
 WHICH THEY ARE AFFIXED.
  
 4)THE INFORMATION SUBMITTED FOR THE STRUCTURE OF THE
 SIGN CONTAINS A PHOTO-COPY SIGNATURE OF THE ENGINEER. A
 PROFESSIONAL ENGINEER SHALL SIGN HIS NAME AND AFFIX HIS
 SEAL TO ALL PLANS=S, SPECIFICATIONS, REPORTS, FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE OWNER'S
 REPRESENTATIVE, OR OTHER COCUMENTS PREPARED OR ISSUED
 BY SAID REGISTRANT, AND BEING FILED FOR PUBLIC RECORD.
 61G15-23.002. SUBMIT ORIGINAL INFORMATION WHICH WILL BE
 KEPT FOR PUBLIC RECORD.
  
 5)2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 6)THE VALUE IS TO LOW.IF, IN THE OPINION OF THE
 BUILDING OFFICIAL, THE CLAIMED VALUATION OF BUILDING,
 ALTERATION, STRUCTURE , ELECTRICAL, GAS, MECHANICAL OR
 PLUMBING SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED. FOR PERMITTING
 PURPOSES, VALUATION OFBUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, NORMAL SITE WORK
 ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD
 AND PROFIT; EXCLUDING LAND. OUR VALUATION REFERENCE IS
 ICC (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS
 SERVICES PER 108.3 FBC*
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726