2007-02-20 18:05:16 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2004 |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| |
| FROM PREVIOUS LIST: |
| |
| 1.)A DETAIL WITH CONNECTION TYPE C3 AND C4 WAS |
| CIRCLED.FOR SPAN OF 15FT, 47.2 PSF, ANCHOR SPACING OF |
| 10INCHES IS NOT COMPLIANT.TO USE "GENERIC" ANCHORING, |
| IT MUST BE COMPLIANT FOR WORST CASE.PLEASE ADDRESS. |
| CHECK ALL OPENINGS. |
| |
| I HAD A TELEPHONE CONVERSATION WITH CONTRACTOR |
| REGARDING THIS CORRECTION.CONTRACTOR INFORMED ME THAT |
| THERE ARE NO OPENINGS OF 15 FEET.THE LARGEST SPAN FOR |
| THIS JOB IS 121", 10 FEET.SEE SHEET 7 OF THE PRODUCT |
| APPROVAL.A 10' SPAN WOULD BE REQUIRED TO USE THE 15' |
| CHART (AS THE NEXT CHART SIZE DOWN IS 9', TOO SMALL FOR |
| THE 10' SPAN).FOR A DESIGN PRESSURE OF -47.2, ANCHOR |
| SPACING RANGES FROM 4INCHES TO 14 INCHES, AND THE |
| 10INCH ANCHOR SPACING WHICH YOU SPECIFY IS NOT |
| COMPLIANT FOR ALL CONNECTION TYPES. |
| |
| THE OTHER OPENINGS ARE LESS THAN 9 FEET.FOR -47.2, |
| ANCHOR SPACING RANGES FROM 7 INCHES TO 18 INCHRES.THE |
| 10INCH SPACING IS STILL NOT COMPLIANT FOR ALL |
| CONNECTION TYPES. |
| |
| ONE NUMBER ON THE ANCHOR SPACING CHART WAS CIRCLED, ALL |
| POINTS SOLID SET, FOR 6' SPAN 2INCH EDGE DISTANCE. |
| ALSO 1/4 ITW TAPCON WAS CIRCLED.IF YOU ARE USING |
| MULTIPLE FASTENER TYPES, PLEASE PROVIDE INFORMATION |
| SPECIFIC TO EACH OPENING OR SPECIFY ANCHOR SPACING TO |
| BE "WORST CASE". |
| |
| TO DECLARE 10" ANCHOR SPACING, YOU MUST SPECIFY WHICH |
| CONNECTION TYPE YOU ARE USING AS NOT ALL OF THEM ARE |
| COMPLIANT.GENERIC ANCHORING (SPECIFYING ONE ANCHOR |
| SPACING FOR THE ENTIRE JOB) MUST BE DESIGNED TO THE |
| WORST CASE AND MUST PROVIDE ALL INFORMATION REQUIRED TO |
| DETERMINE CODE COMPLIANCE. |
| |
| |
| |
| |
| |