Plan Review Notes For Permit 07011078 |
Permit Number |
07011078 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-02-09 09:52:02 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2004 | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | 1.)A DETAIL WITH CONNECTION TYPE C3 AND C4 WAS | | CIRCLED.FOR SPAN OF 15FT, 47.2 PSF, ANCHOR SPACING OF | | 10INCHES IS NOT COMPLIANT.TO USE "GENERIC" ANCHORING, | | IT MUST BE COMPLIANT FOR WORST CASE.PLEASE ADDRESS. | | CHECK ALL OPENINGS. | | | | |
|