Plan Review Notes
Plan Review Notes For Permit 07011070
Permit Number 07011070
Review Stop E
Sequence Number 2
Notes
Date Text
2007-06-12 07:57:00 
  
 DENIED/INCOMPLETE INFORMATION
  
 1} THERE MUST BE A DISCONNECTING MEANS FOR THE PANELS
 SHOWN PER 230.70(A)(1) AND 225.32, THE PANEL IS LISTED
 AS MAIN LUG ONLY. INDICATE IF THE PANEL IS AT THE
 SERVICE AND IF SO SHOW COMPLIANCE WITH THE ABOVE
 ARTICLES.
  
 2} IF THE FIRST FLOOR IS INCLUDED IN THE ELECTRICAL
 WORK UNDER THIS PERMIT, PROVIDE A PANEL SCHEDULE PER
 408.4 NEC 2005, ALSO CALCULATE THE ENTIRE SERVICE PER
 220.
  
 3} THERE ARE NONE OF THE REQUIREDGFI CIRCUITS (210.8)
 SHOWN ON THE FIRST FLOOR. PLEASE SHOW ONLY THE WORK TO
 BE DONE UNDER THIS PERMIT.
  
 THERE IS NO ELECTRICAL WORK INDICATED ON THE
 APPLICATION. CORRECT APPLICATION TO INCLUDE ALL WORK TO
 BE PERMITTED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718