2007-03-20 08:58:32 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBEXISTING BUILDING CODE 2004 |
| FBC R RESIDENTIAL 2004 |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE |
| FBC2004 |
| |
| 1.)PROVIDE A ROOF FRAMING PLAN, FBC*106.3.5.SHOW |
| THE SCOPE OF WORK.THE EXTENT OF DAMAGE IS NOT CLEAR. |
| IT APPEARS THAT YOU ARE INSTALLING NEW ROOF FRAMING, |
| BUT THE PLAN SHOWS THAT THE FIRST FLOOR HAS NO DAMAGE. |
| IF THERE IS NO ROOF ON THE BUILDING, HOW HAS IT |
| REMAINED DRY ON THE FIRST FLOOR WITH NO DAMAGE?IF YOU |
| ARE NOT REPLACING ALL ROOF FRAMING, SHOW EXTENT OF THE |
| REPAIRS ON A PLAN. |
| |
| 2.)DECLARE WIND DESIGN CRITERIA, FBC R 301.2 (WIND |
| SPEED, EXPOSURE CATEGORY, DESIGN PRESSURE FOR |
| COMPONENTS & CLADDING). |
| |
| 3.)PROVIDE OVERALL DIMENSIONS ON THE FLOOR PLAN. |
| |
| 4.)THERE IS A NOTE ON THE PLAN TO INCREASE WINDOW TO |
| 24 ESCAPE.A 24 WINDOW DOES NOT COMPLY WITH EMERGENCY |
| EGRESS REQUIREMENTS OF FBC310.1.HOWEVER, PLEASE SEE |
| FBC EB 505.1.DESIGN INTENT IS NOT CLEAR. |
| |
| 5.)REVISED 4/27 - IMPACT PROTECTION REQUIRED FBC R |
| 301.2.1.2.SEE ATTACHED POLICY IN REGARDS TO REMOVABLE |
| SHUTTERS ON COMMERCIAL BUILDINGS.THIS IS NOT ALLOWED |
| ON THE SECOND FLOOR.IF NONIMPACT GLASS WITH FIXED |
| SHUTTERS ARE USED, A PLAN MUST BE SUBMITTED TO THE |
| BUILDING OFFICIAL.PLEASE CONTACT ME IF YOU NEED |
| ASSISTANCE WITH THIS ITEM. |
| |
| 6.)DECLARE GOVERNING CODE, INCLUDING FBC EB, AND |
| DECLARE LEVEL OF ALTERATION FBC EB CHAPTER 3. |
| |
| 7.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER |
| OF RECORD, FBC*106.3.3. |
| |
| 8.)SUBMIT PRODUCT APPROVALS FOR THE ROOF, SHUTTERS IF |
| APPLICABLE, AND THE DOORS. |
| |
| 9.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED |
| IN ADDITION TO THE NOAS SUBMITTED, FAC9B72. |
| WWW.FLORIDABUILDING.ORG |
| |
| 10.)THE WINDOW AT THE TUB IS IN A HAZARDOUS LOCATION, |
| FBC R308.4.NOTE SAFETY GLAZING REQUIREMENT ON THE |
| PLAN. |
| |
| 11.)SHOW FIRE RESISTANCE REQUIREMENTS AND A DETAIL |
| FOR PENETRATIONS FBC R317.1, FBC R317.3. |
| |
| 12.)ATTIC ACCESS REQUIRED FBC R807. |
| |