2007-03-09 16:33:34 | *** DENIED *** |
| 1) PLEASE SUBMIT DETAILED MANUFACTURER'S |
| SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR AIR |
| HANDLER AND 10 KW HEATER, AS A 10 KW HEATER APPEARS TO |
| LARGE FOR A 1 1/2 TON AIR HANDLER. |
| |
| 2) PLEASE SHOW THE SIZE OF THE RETURN AIR TRANSFER |
| GRILLS ON PLANS, SEE 2004 FBC/R M1602.4 (B). |
| |
| ***2004 FBC/R M1602.4. BALANCED RETURN AIR MAY BE |
| ACHIEVED BY. |
| (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE |
| RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS |
| SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT |
| ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR |
| HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO |
| ACHIEVE PROPER RETURN AIR BALANCE. |
| (B)TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (OF |
| GRILLE AREA) TO 100 CFM (OF SUPPLY AIR) FOR SIZING |
| THROUGH-THE-WALL TRANSFER GRILLES AND USING AN |
| UNRESTRICTED 1-INCH UNDERCUTTING OF DOORS TO ACHIEVE |
| PROPER RETURN AIR BALANCE |
| (C)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET |
| THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR |
| EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY |
| ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE |
| SHALL BE INCLUDED. |
| |
| MECHANICAL PLAN REVIEW BY; |
| TOM GORDON (561) 805-6729. |