Plan Review Notes For Permit 07011070 |
Permit Number |
07011070 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-03-08 16:32:58 | | | | | DENIED/INCOMPLETE INFORMATION | | | | 1} LOCATE THE PANEL ON THE PLAN, IF THERE IS NO PANEL | | ON THE2ND FLOOR, THEN THE PANEL SHOWN COULD NOT BE | | MLO AS INDICATED. | | | | 2} PROVIDE A PANEL SCHEDULE PER 408.4. PLEASE SEE NEW | | VERBAGE FOR 2005 NEC: "THE IDENTIFICATION SHALL INCLUDE | | SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE | | DISTINGUISHED FROM ALL OTHERS." SEE 210.52 FOR REQUIRED | | OUTLETS. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|