2007-03-08 16:32:58 
  
 DENIED/INCOMPLETE INFORMATION
  
 1} LOCATE THE PANEL ON THE PLAN, IF THERE IS NO PANEL
 ON THE2ND FLOOR, THEN THE PANEL SHOWN COULD NOT BE
 MLO AS INDICATED.
  
 2} PROVIDE A PANEL SCHEDULE PER 408.4. PLEASE SEE NEW
 VERBAGE FOR 2005 NEC: "THE IDENTIFICATION SHALL INCLUDE
 SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS." SEE 210.52 FOR REQUIRED
 OUTLETS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  