Plan Review Notes
Plan Review Notes For Permit 07011041
Permit Number 07011041
Review Stop M
Sequence Number 1
Notes
Date Text
2007-02-08 13:54:16*** DENIED ***
 1) SEE BUILDING REVIEW NOTE #2, PLEASE CORRECT.
  
 2) PLEASE CORRECT JOB ADDRESS IN TITLE BLOCK (444 W.
 RAILROAD AVE. SUITE 430).
  
 3) BE ADVISED A NOTICE OF COMMENCEMENT WILL NEED TO BE
 FILED AS THIS PERMIT 07011041 FOR TENANT IMPROVEMENT IS
 NOT IN THE SCOPE OF PERMIT 04042022 WHICH CAN NOT BE
 USED AS A MASTER PERMIT, PER ROBERT BROWN SERVICES
 MANAGER.
  
 4) THE RETURN AIR TRANSFER DUCTS TO OFFICES 1, 2, 3, 4,
 AND CONFERENCE ROOM ARE UNDER-SIZED. BALANCED RETURN
 AIR MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS
 SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR
 HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO
 ACHIEVE PROPER RETURN AIR BALANCE. PER 2004 FBC/R
 M1602.4 . PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.