Notes |
Date |
Text |
2007-02-08 13:54:16 | *** DENIED *** | | 1) SEE BUILDING REVIEW NOTE #2, PLEASE CORRECT. | | | | 2) PLEASE CORRECT JOB ADDRESS IN TITLE BLOCK (444 W. | | RAILROAD AVE. SUITE 430). | | | | 3) BE ADVISED A NOTICE OF COMMENCEMENT WILL NEED TO BE | | FILED AS THIS PERMIT 07011041 FOR TENANT IMPROVEMENT IS | | NOT IN THE SCOPE OF PERMIT 04042022 WHICH CAN NOT BE | | USED AS A MASTER PERMIT, PER ROBERT BROWN SERVICES | | MANAGER. | | | | 4) THE RETURN AIR TRANSFER DUCTS TO OFFICES 1, 2, 3, 4, | | AND CONFERENCE ROOM ARE UNDER-SIZED. BALANCED RETURN | | AIR MAY BE ACHIEVED BY. | | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE | | RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS | | SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT | | ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR | | HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO | | ACHIEVE PROPER RETURN AIR BALANCE. PER 2004 FBC/R | | M1602.4 . PLEASE CORRECT. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|