2007-02-06 12:43:16*****DENIED*****
  
  
 01.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE
 PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED.
  
 02. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 03.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT
 OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 04.THE COMPLETE ADDRESS OF WHERE THE SCOPE OF WORK
 WILL BE CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.
  
 05.DISPLAY THE TENANT SPACE NUMBER FOR THIS SITE SO
 THAT IT IS DISTINGUISHABLE FROM OTHER TENANT SITES ON
 THE FLOOR.AS PER WEST PALM BEACH CODE, THOSE NUMBERS
 SHALL BE NO LESS THAN 3" IN HEIGHT.
  
 06.DOOR(S) LEADING DIRECTLY TO THE FOURTH FLOOR
 CORRIDOR SHALL BE AN APPROVED, LISTED, AND LABELED FIRE
 DOOR & ASSEMBLY IN ACCORDANCE WITH THE REQUIREMENTS OF
 NFPA 80.
  
 07.WHAT IS INTERIOR FINISH CLASSIFICATION FOR THE
 WALLS AND CEILINGS IN THE EXITS, EXIT ACCESS CORRIDORS,
 AND IN ALL OTHER AREAS?
  
 08.PROVIDE A LIFE SAFETY PLAN SHEET WHICH INDICATES
 THE TRAVEL DISTANCE TO THE EXIT(S).ALSO ON THIS
 SHEET, INDICATE THE LOCATION OFFIRE EXTINGUISHER(S)
 AT DISTANCES TO SATISFY THE 75' TRAVEL DISTANCE
 REQUIREMENT.
  
 09.ON SHEET FA0.1, FIRE ALARM NOTE #17 SHOULD BE
 CHANGED TO "INITIATE A GENERAL FIRE ALARM".
  
 10.PROVIDE A LAYOUT OF THE FIRE SPRINKLER SYSTEM FOR
 THIS TENANT SPACE.
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED ON THE PLAN.
  
  